Re: Very slightly OT: Circuit breaker compatibility

From Joerg <news@analogconsultants.com>
Newsgroups sci.electronics.design
Subject Re: Very slightly OT: Circuit breaker compatibility
Date 2017-03-16 10:37 -0700
Message-ID <ej00pvFi7skU1@mid.individual.net> (permalink)
References (9 earlier) <oa46l3$t1b$1@dont-email.me> <eio65pF11dfU1@mid.individual.net> <oac5t5$svd$1@dont-email.me> <eivnl9FgafjU1@mid.individual.net> <b7d482b0-6d89-439f-9bf1-3b348dfa4dce@googlegroups.com>

Show all headers | View raw


On 2017-03-16 10:19, tabbypurr@gmail.com wrote:
> On Thursday, 16 March 2017 15:01:04 UTC, Joerg  wrote:
>> On 2017-03-15 12:52, Don Y wrote:
>>> On 3/13/2017 11:19 AM, Joerg wrote:
>>>> On 2017-03-12 12:16, Don Y wrote:
>>>>> On 3/12/2017 8:16 AM, Joerg wrote:
>
>> A trip is nearly always a ground fault. In about 20 years didn't
>> have a circuit breaker trip for overcurrent or a short. The first
>> couple of trips after buying the house were because I came from
>> Europe and had to get used to the fact that US power circuits only
>> deliver half the watts. We did have ground fault trips. Then there
>> is the cost.
>>
>> Breaker with integrated GFCI: $50.
>>
>> Normal breaker plus GFCI outlet: $5 plus $10, and you get a free
>> outlet.
>
> both seem a bit steep
>

GFCI outlets used to be around $5. "There is no inflation, trust us".
Yeah, right.

The breakers with integrated GFCI are a rip-off IMHO. The clerk at the 
store used to be an electrician and when I said I rather use a regular 
breaker and GFCI outlet he smiled and nodded knowingly.

>
>>>>> Most homes of this vintage have a single circuit feeding two
>>>>> or more bathrooms (because the lighting circuit there isn't
>>>>> GFCI).  Especially true when multiple bathrooms tend to share
>>>>> a wet wall -- the electric outlets in each bathroom will tend
>>>>> to be as closely sited as the water closets!
>>>>
>>>> Not a good design and luckily not done that way in our 1970
>>>> house.
>>>
>>> In our 1980 house, that's the way it is.  The same was true of
>>> the 1950 home that I grew up in.
>
> Almost all houses here have breakers feed several rooms. I've not
> found it to be a problem.
>

Until someone turns a bedroom into an office.


>>> It's only recent construction that has opted to put more branch
>>> circuits in place in rooms other than the kitchen.
>
> radial circuits however are a safety issue.
>

Why?


>> My wife was house hunting and I was the QC guy. There were several
>> red flags I watched out for. If the glasses in a hutch clinked when
>> I jumped a bit in the center of a room that was one. If I found too
>> few breakers for the number of rooms that was another.
>
> I take it you've not spent time in the uk. Some houses shake if you
> jump on the floor. Lots of houses & flats still run on 4 fuses total,
> no GFCI.
>

I lived on the upper floor of a free-standing house near Aberdeen for a 
short while. That house had solid granite blocks as outer walls and was 
the sturdies place I ever lived in. The neighboring homes were built 
that way as well. IIRC each outlet had its own little fuse of 13A or so 
locally.


>> I really do not like it when my wife uses the hair dryer, I turn on
>> the shop vac or printer and then a breaker clicks off.
>>
>> This might have to do with the fact that I lived in Europe before
>> and the adjustment to the typical US circuit size was sobering.
>> Almost everything is bigger in the US but not electrical circuits.
>> In Europe we had over 3600W per circuit so running the vaccuum plus
>> laser printing was no problem. Here all we get is 1800W on most and
>> 2400W on the few 20A circuits. Which really puts a crimp into my
>> home brewing activities.
>
> A tyipcal socket circuit here has a 32A breaker providing 7.68kW
> continuous, and much more short term. It's common to run 45 or 50A
> short term as multiple appliances heat simultaneously.
>

32A is even better though in the UK each regular socket is limited to 
13A while in Germany that is 16A:

http://www.electricalsafetyfirst.org.uk/guides-and-advice/electrical-items/amps-and-watts/

In the US you can have a NEMA outlet for 240V/20A but that's a custom 
installation. Except in the garage in newer homes where a 240V/30A 
outlet is often required to enable the use of electric vehicles. 
Unfortunately I can't do my home brewing in the garage because there is 
no sink and it's too hot there in summer and too cold in winter. And 
there is no pool table :-)

-- 
Regards, Joerg

http://www.analogconsultants.com/

Back to sci.electronics.design | Previous | Next — Previous in thread | Next in thread | Find similar | Unroll thread


Thread

Very slightly OT: Circuit breaker compatibility Joerg <news@analogconsultants.com> - 2017-03-11 11:53 -0800
  Re: Very slightly OT: Circuit breaker compatibility Jim Thompson <To-Email-Use-The-Envelope-Icon@On-My-Web-Site.com> - 2017-03-11 13:03 -0700
    Re: Very slightly OT: Circuit breaker compatibility Joerg <news@analogconsultants.com> - 2017-03-11 12:31 -0800
      Re: Very slightly OT: Circuit breaker compatibility tabbypurr@gmail.com - 2017-03-11 18:36 -0800
        Re: Very slightly OT: Circuit breaker compatibility Joerg <news@analogconsultants.com> - 2017-03-12 07:10 -0700
  Re: Very slightly OT: Circuit breaker compatibility Don Y <blockedofcourse@foo.invalid> - 2017-03-11 13:09 -0700
    Re: Very slightly OT: Circuit breaker compatibility Joerg <news@analogconsultants.com> - 2017-03-11 12:34 -0800
      Re: Very slightly OT: Circuit breaker compatibility Don Y <blockedofcourse@foo.invalid> - 2017-03-11 14:13 -0700
        Re: Very slightly OT: Circuit breaker compatibility Joerg <news@analogconsultants.com> - 2017-03-11 16:00 -0800
          Re: Very slightly OT: Circuit breaker compatibility Don Y <blockedofcourse@foo.invalid> - 2017-03-11 17:22 -0700
            Re: Very slightly OT: Circuit breaker compatibility krw@notreal.com - 2017-03-11 21:40 -0500
            Re: Very slightly OT: Circuit breaker compatibility Joerg <news@analogconsultants.com> - 2017-03-12 07:07 -0700
              Re: Very slightly OT: Circuit breaker compatibility Don Y <blockedofcourse@foo.invalid> - 2017-03-12 07:59 -0700
                Re: Very slightly OT: Circuit breaker compatibility Joerg <news@analogconsultants.com> - 2017-03-12 08:16 -0700
                Re: Very slightly OT: Circuit breaker compatibility Don Y <blockedofcourse@foo.invalid> - 2017-03-12 12:16 -0700
                Re: Very slightly OT: Circuit breaker compatibility Joerg <news@analogconsultants.com> - 2017-03-13 11:19 -0700
                Re: Very slightly OT: Circuit breaker compatibility Don Y <blockedofcourse@foo.invalid> - 2017-03-15 12:52 -0700
                Re: Very slightly OT: Circuit breaker compatibility Joerg <news@analogconsultants.com> - 2017-03-16 08:01 -0700
                Re: Very slightly OT: Circuit breaker compatibility tabbypurr@gmail.com - 2017-03-16 10:19 -0700
                Re: Very slightly OT: Circuit breaker compatibility Joerg <news@analogconsultants.com> - 2017-03-16 10:37 -0700
                Re: Very slightly OT: Circuit breaker compatibility tabbypurr@gmail.com - 2017-03-16 16:12 -0700
                Re: Very slightly OT: Circuit breaker compatibility Joerg <news@analogconsultants.com> - 2017-03-16 16:33 -0700
                Re: Very slightly OT: Circuit breaker compatibility tabbypurr@gmail.com - 2017-03-16 20:15 -0700
                Re: Very slightly OT: Circuit breaker compatibility krw@notreal.com - 2017-03-12 20:43 -0400
                Re: Very slightly OT: Circuit breaker compatibility tabbypurr@gmail.com - 2017-03-13 02:05 -0700
                Re: Very slightly OT: Circuit breaker compatibility krw@notreal.com - 2017-03-13 21:33 -0400
                Re: Very slightly OT: Circuit breaker compatibility tabbypurr@gmail.com - 2017-03-14 06:38 -0700
                Re: Very slightly OT: Circuit breaker compatibility krw@notreal.com - 2017-03-14 12:47 -0400
                Re: Very slightly OT: Circuit breaker compatibility Joerg <news@analogconsultants.com> - 2017-03-14 12:00 -0700
                Re: Very slightly OT: Circuit breaker compatibility krw@notreal.com - 2017-03-14 20:44 -0400
                Re: Very slightly OT: Circuit breaker compatibility tabbypurr@gmail.com - 2017-03-15 05:53 -0700
                Re: Very slightly OT: Circuit breaker compatibility krw@notreal.com - 2017-03-15 12:53 -0400
                Re: Very slightly OT: Circuit breaker compatibility kevin93 <kevin@whitedigs.com> - 2017-03-15 15:11 -0700
                Re: Very slightly OT: Circuit breaker compatibility tabbypurr@gmail.com - 2017-03-15 16:34 -0700
                Re: Very slightly OT: Circuit breaker compatibility krw@notreal.com - 2017-03-15 20:38 -0400
                Re: Very slightly OT: Circuit breaker compatibility Joerg <news@analogconsultants.com> - 2017-03-16 08:03 -0700
                Re: Very slightly OT: Circuit breaker compatibility krw@notreal.com - 2017-03-16 20:36 -0400
                Re: Very slightly OT: Circuit breaker compatibility Joerg <news@analogconsultants.com> - 2017-03-17 16:54 -0700
                Re: Very slightly OT: Circuit breaker compatibility krw@notreal.com - 2017-03-17 22:35 -0400
                Re: Very slightly OT: Circuit breaker compatibility Joerg <news@analogconsultants.com> - 2017-03-18 07:42 -0700
                Re: Very slightly OT: Circuit breaker compatibility krw@notreal.com - 2017-03-18 10:47 -0400
                Re: Very slightly OT: Circuit breaker compatibility Jasen Betts <jasen@xnet.co.nz> - 2017-03-14 05:12 +0000
                Re: Very slightly OT: Circuit breaker compatibility krw@notreal.com - 2017-03-14 12:48 -0400
                Re: Very slightly OT: Circuit breaker compatibility Joerg <news@analogconsultants.com> - 2017-03-13 11:20 -0700
                Re: Very slightly OT: Circuit breaker compatibility krw@notreal.com - 2017-03-12 20:39 -0400
                Re: Very slightly OT: Circuit breaker compatibility whit3rd <whit3rd@gmail.com> - 2017-03-13 16:53 -0700
                Re: Very slightly OT: Circuit breaker compatibility Don Y <blockedofcourse@foo.invalid> - 2017-03-13 17:13 -0700
                Re: Very slightly OT: Circuit breaker compatibility Joerg <news@analogconsultants.com> - 2017-03-14 08:06 -0700
              Re: Very slightly OT: Circuit breaker compatibility krw@notreal.com - 2017-03-12 20:36 -0400
                Re: Very slightly OT: Circuit breaker compatibility Joerg <news@analogconsultants.com> - 2017-03-13 11:54 -0700
      Re: Very slightly OT: Circuit breaker compatibility Lasse Langwadt Christensen <langwadt@fonz.dk> - 2017-03-11 13:27 -0800
        Re: Very slightly OT: Circuit breaker compatibility Joerg <news@analogconsultants.com> - 2017-03-11 16:02 -0800
          Re: Very slightly OT: Circuit breaker compatibility Lasse Langwadt Christensen <langwadt@fonz.dk> - 2017-03-11 16:33 -0800
            Re: Very slightly OT: Circuit breaker compatibility Joerg <news@analogconsultants.com> - 2017-03-12 07:14 -0700
              Re: Very slightly OT: Circuit breaker compatibility tabbypurr@gmail.com - 2017-03-12 11:38 -0700
                Re: Very slightly OT: Circuit breaker compatibility Joerg <news@analogconsultants.com> - 2017-03-13 15:49 -0700
                Re: Very slightly OT: Circuit breaker compatibility tabbypurr@gmail.com - 2017-03-14 06:40 -0700
                Re: Very slightly OT: Circuit breaker compatibility Joerg <news@analogconsultants.com> - 2017-03-14 07:59 -0700
                Re: Very slightly OT: Circuit breaker compatibility krw@notreal.com - 2017-03-14 12:51 -0400
                Re: Very slightly OT: Circuit breaker compatibility Joerg <news@analogconsultants.com> - 2017-03-14 11:57 -0700
                Re: Very slightly OT: Circuit breaker compatibility Lasse Langwadt Christensen <langwadt@fonz.dk> - 2017-03-14 14:01 -0700
                Re: Very slightly OT: Circuit breaker compatibility Joerg <news@analogconsultants.com> - 2017-03-14 14:21 -0700
                Re: Very slightly OT: Circuit breaker compatibility tabbypurr@gmail.com - 2017-03-14 16:59 -0700
                Re: Very slightly OT: Circuit breaker compatibility Chris Jones <lugnut808@spam.yahoo.com> - 2017-03-16 00:50 +1100
                Re: Very slightly OT: Circuit breaker compatibility tabbypurr@gmail.com - 2017-03-15 07:26 -0700
                Re: Very slightly OT: Circuit breaker compatibility Lasse Langwadt Christensen <langwadt@fonz.dk> - 2017-03-15 11:17 -0700
                Re: Very slightly OT: Circuit breaker compatibility tabbypurr@gmail.com - 2017-03-15 16:31 -0700
                Re: Very slightly OT: Circuit breaker compatibility Lasse Langwadt Christensen <langwadt@fonz.dk> - 2017-03-15 16:59 -0700
                Re: Very slightly OT: Circuit breaker compatibility tabbypurr@gmail.com - 2017-03-15 19:06 -0700
                Re: Very slightly OT: Circuit breaker compatibility Chris Jones <lugnut808@spam.yahoo.com> - 2017-03-16 23:26 +1100
                Re: Very slightly OT: Circuit breaker compatibility tabbypurr@gmail.com - 2017-03-16 10:12 -0700
                Re: Very slightly OT: Circuit breaker compatibility krw@notreal.com - 2017-03-14 20:47 -0400
                Re: Very slightly OT: Circuit breaker compatibility krw@notreal.com - 2017-03-14 20:47 -0400
                Re: Very slightly OT: Circuit breaker compatibility Joerg <news@analogconsultants.com> - 2017-03-16 08:06 -0700
                Re: Very slightly OT: Circuit breaker compatibility "Michael A. Terrell" <mike.terrell@earthlink.net> - 2017-03-17 16:29 -0400
                Re: Very slightly OT: Circuit breaker compatibility krw@notreal.com - 2017-03-17 22:39 -0400
                Re: Very slightly OT: Circuit breaker compatibility tabbypurr@gmail.com - 2017-03-18 01:52 -0700
                Re: Very slightly OT: Circuit breaker compatibility krw@notreal.com - 2017-03-18 09:45 -0400
                Re: Very slightly OT: Circuit breaker compatibility tabbypurr@gmail.com - 2017-03-18 07:37 -0700
                Re: Very slightly OT: Circuit breaker compatibility krw@notreal.com - 2017-03-18 10:48 -0400
                Re: Very slightly OT: Circuit breaker compatibility tabbypurr@gmail.com - 2017-03-18 09:18 -0700
                Re: Very slightly OT: Circuit breaker compatibility krw@notreal.com - 2017-03-18 14:13 -0400
                Re: Very slightly OT: Circuit breaker compatibility tabbypurr@gmail.com - 2017-03-18 13:20 -0700
                Re: Very slightly OT: Circuit breaker compatibility krw@notreal.com - 2017-03-18 20:00 -0400
                Re: Very slightly OT: Circuit breaker compatibility tabbypurr@gmail.com - 2017-03-18 18:40 -0700
                Re: Very slightly OT: Circuit breaker compatibility krw@notreal.com - 2017-03-18 22:17 -0400
                Re: Very slightly OT: Circuit breaker compatibility "Michael A. Terrell" <mike.terrell@earthlink.net> - 2017-03-19 12:14 -0400
    ) Spehro Pefhany <speffSNIP@interlogDOTyou.knowwhat> - 2017-03-12 01:12 -0500
      Re: ) tabbypurr@gmail.com - 2017-03-12 03:51 -0700
  Re: Very slightly OT: Circuit breaker compatibility Tim Wescott <tim@seemywebsite.really> - 2017-03-11 14:27 -0600
    Re: Very slightly OT: Circuit breaker compatibility Joerg <news@analogconsultants.com> - 2017-03-11 12:38 -0800
      Re: Very slightly OT: Circuit breaker compatibility Chris Jones <lugnut808@spam.yahoo.com> - 2017-03-12 23:57 +1100
        Re: Very slightly OT: Circuit breaker compatibility Joerg <news@analogconsultants.com> - 2017-03-12 07:17 -0700
  Re: Very slightly OT: Circuit breaker compatibility Jon Elson <elson@pico-systems.com> - 2017-03-11 20:14 -0600

csiph-web