Very slightly OT: Circuit breaker compatibility

Started byJoerg <news@analogconsultants.com>
First post2017-03-11 11:53 -0800
Last post2017-03-11 20:14 -0600
Articles 20 on this page of 94 — 14 participants

Back to article view | Back to sci.electronics.design


Contents

  Very slightly OT: Circuit breaker compatibility Joerg <news@analogconsultants.com> - 2017-03-11 11:53 -0800
    Re: Very slightly OT: Circuit breaker compatibility Jim Thompson <To-Email-Use-The-Envelope-Icon@On-My-Web-Site.com> - 2017-03-11 13:03 -0700
      Re: Very slightly OT: Circuit breaker compatibility Joerg <news@analogconsultants.com> - 2017-03-11 12:31 -0800
        Re: Very slightly OT: Circuit breaker compatibility tabbypurr@gmail.com - 2017-03-11 18:36 -0800
          Re: Very slightly OT: Circuit breaker compatibility Joerg <news@analogconsultants.com> - 2017-03-12 07:10 -0700
    Re: Very slightly OT: Circuit breaker compatibility Don Y <blockedofcourse@foo.invalid> - 2017-03-11 13:09 -0700
      Re: Very slightly OT: Circuit breaker compatibility Joerg <news@analogconsultants.com> - 2017-03-11 12:34 -0800
        Re: Very slightly OT: Circuit breaker compatibility Don Y <blockedofcourse@foo.invalid> - 2017-03-11 14:13 -0700
          Re: Very slightly OT: Circuit breaker compatibility Joerg <news@analogconsultants.com> - 2017-03-11 16:00 -0800
            Re: Very slightly OT: Circuit breaker compatibility Don Y <blockedofcourse@foo.invalid> - 2017-03-11 17:22 -0700
              Re: Very slightly OT: Circuit breaker compatibility krw@notreal.com - 2017-03-11 21:40 -0500
              Re: Very slightly OT: Circuit breaker compatibility Joerg <news@analogconsultants.com> - 2017-03-12 07:07 -0700
                Re: Very slightly OT: Circuit breaker compatibility Don Y <blockedofcourse@foo.invalid> - 2017-03-12 07:59 -0700
                  Re: Very slightly OT: Circuit breaker compatibility Joerg <news@analogconsultants.com> - 2017-03-12 08:16 -0700
                    Re: Very slightly OT: Circuit breaker compatibility Don Y <blockedofcourse@foo.invalid> - 2017-03-12 12:16 -0700
                      Re: Very slightly OT: Circuit breaker compatibility Joerg <news@analogconsultants.com> - 2017-03-13 11:19 -0700
                        Re: Very slightly OT: Circuit breaker compatibility Don Y <blockedofcourse@foo.invalid> - 2017-03-15 12:52 -0700
                          Re: Very slightly OT: Circuit breaker compatibility Joerg <news@analogconsultants.com> - 2017-03-16 08:01 -0700
                            Re: Very slightly OT: Circuit breaker compatibility tabbypurr@gmail.com - 2017-03-16 10:19 -0700
                              Re: Very slightly OT: Circuit breaker compatibility Joerg <news@analogconsultants.com> - 2017-03-16 10:37 -0700
                                Re: Very slightly OT: Circuit breaker compatibility tabbypurr@gmail.com - 2017-03-16 16:12 -0700
                                  Re: Very slightly OT: Circuit breaker compatibility Joerg <news@analogconsultants.com> - 2017-03-16 16:33 -0700
                                    Re: Very slightly OT: Circuit breaker compatibility tabbypurr@gmail.com - 2017-03-16 20:15 -0700
                    Re: Very slightly OT: Circuit breaker compatibility krw@notreal.com - 2017-03-12 20:43 -0400
                      Re: Very slightly OT: Circuit breaker compatibility tabbypurr@gmail.com - 2017-03-13 02:05 -0700
                        Re: Very slightly OT: Circuit breaker compatibility krw@notreal.com - 2017-03-13 21:33 -0400
                          Re: Very slightly OT: Circuit breaker compatibility tabbypurr@gmail.com - 2017-03-14 06:38 -0700
                            Re: Very slightly OT: Circuit breaker compatibility krw@notreal.com - 2017-03-14 12:47 -0400
                              Re: Very slightly OT: Circuit breaker compatibility Joerg <news@analogconsultants.com> - 2017-03-14 12:00 -0700
                                Re: Very slightly OT: Circuit breaker compatibility krw@notreal.com - 2017-03-14 20:44 -0400
                                  Re: Very slightly OT: Circuit breaker compatibility tabbypurr@gmail.com - 2017-03-15 05:53 -0700
                                    Re: Very slightly OT: Circuit breaker compatibility krw@notreal.com - 2017-03-15 12:53 -0400
                                    Re: Very slightly OT: Circuit breaker compatibility kevin93 <kevin@whitedigs.com> - 2017-03-15 15:11 -0700
                                      Re: Very slightly OT: Circuit breaker compatibility tabbypurr@gmail.com - 2017-03-15 16:34 -0700
                                      Re: Very slightly OT: Circuit breaker compatibility krw@notreal.com - 2017-03-15 20:38 -0400
                                        Re: Very slightly OT: Circuit breaker compatibility Joerg <news@analogconsultants.com> - 2017-03-16 08:03 -0700
                                          Re: Very slightly OT: Circuit breaker compatibility krw@notreal.com - 2017-03-16 20:36 -0400
                                            Re: Very slightly OT: Circuit breaker compatibility Joerg <news@analogconsultants.com> - 2017-03-17 16:54 -0700
                                              Re: Very slightly OT: Circuit breaker compatibility krw@notreal.com - 2017-03-17 22:35 -0400
                                                Re: Very slightly OT: Circuit breaker compatibility Joerg <news@analogconsultants.com> - 2017-03-18 07:42 -0700
                                                  Re: Very slightly OT: Circuit breaker compatibility krw@notreal.com - 2017-03-18 10:47 -0400
                        Re: Very slightly OT: Circuit breaker compatibility Jasen Betts <jasen@xnet.co.nz> - 2017-03-14 05:12 +0000
                          Re: Very slightly OT: Circuit breaker compatibility krw@notreal.com - 2017-03-14 12:48 -0400
                      Re: Very slightly OT: Circuit breaker compatibility Joerg <news@analogconsultants.com> - 2017-03-13 11:20 -0700
                  Re: Very slightly OT: Circuit breaker compatibility krw@notreal.com - 2017-03-12 20:39 -0400
                  Re: Very slightly OT: Circuit breaker compatibility whit3rd <whit3rd@gmail.com> - 2017-03-13 16:53 -0700
                    Re: Very slightly OT: Circuit breaker compatibility Don Y <blockedofcourse@foo.invalid> - 2017-03-13 17:13 -0700
                      Re: Very slightly OT: Circuit breaker compatibility Joerg <news@analogconsultants.com> - 2017-03-14 08:06 -0700
                Re: Very slightly OT: Circuit breaker compatibility krw@notreal.com - 2017-03-12 20:36 -0400
                  Re: Very slightly OT: Circuit breaker compatibility Joerg <news@analogconsultants.com> - 2017-03-13 11:54 -0700
        Re: Very slightly OT: Circuit breaker compatibility Lasse Langwadt Christensen <langwadt@fonz.dk> - 2017-03-11 13:27 -0800
          Re: Very slightly OT: Circuit breaker compatibility Joerg <news@analogconsultants.com> - 2017-03-11 16:02 -0800
            Re: Very slightly OT: Circuit breaker compatibility Lasse Langwadt Christensen <langwadt@fonz.dk> - 2017-03-11 16:33 -0800
              Re: Very slightly OT: Circuit breaker compatibility Joerg <news@analogconsultants.com> - 2017-03-12 07:14 -0700
                Re: Very slightly OT: Circuit breaker compatibility tabbypurr@gmail.com - 2017-03-12 11:38 -0700
                  Re: Very slightly OT: Circuit breaker compatibility Joerg <news@analogconsultants.com> - 2017-03-13 15:49 -0700
                    Re: Very slightly OT: Circuit breaker compatibility tabbypurr@gmail.com - 2017-03-14 06:40 -0700
                      Re: Very slightly OT: Circuit breaker compatibility Joerg <news@analogconsultants.com> - 2017-03-14 07:59 -0700
                        Re: Very slightly OT: Circuit breaker compatibility krw@notreal.com - 2017-03-14 12:51 -0400
                          Re: Very slightly OT: Circuit breaker compatibility Joerg <news@analogconsultants.com> - 2017-03-14 11:57 -0700
                            Re: Very slightly OT: Circuit breaker compatibility Lasse Langwadt Christensen <langwadt@fonz.dk> - 2017-03-14 14:01 -0700
                              Re: Very slightly OT: Circuit breaker compatibility Joerg <news@analogconsultants.com> - 2017-03-14 14:21 -0700
                                Re: Very slightly OT: Circuit breaker compatibility tabbypurr@gmail.com - 2017-03-14 16:59 -0700
                                  Re: Very slightly OT: Circuit breaker compatibility Chris Jones <lugnut808@spam.yahoo.com> - 2017-03-16 00:50 +1100
                                    Re: Very slightly OT: Circuit breaker compatibility tabbypurr@gmail.com - 2017-03-15 07:26 -0700
                                      Re: Very slightly OT: Circuit breaker compatibility Lasse Langwadt Christensen <langwadt@fonz.dk> - 2017-03-15 11:17 -0700
                                        Re: Very slightly OT: Circuit breaker compatibility tabbypurr@gmail.com - 2017-03-15 16:31 -0700
                                          Re: Very slightly OT: Circuit breaker compatibility Lasse Langwadt Christensen <langwadt@fonz.dk> - 2017-03-15 16:59 -0700
                                            Re: Very slightly OT: Circuit breaker compatibility tabbypurr@gmail.com - 2017-03-15 19:06 -0700
                                              Re: Very slightly OT: Circuit breaker compatibility Chris Jones <lugnut808@spam.yahoo.com> - 2017-03-16 23:26 +1100
                                                Re: Very slightly OT: Circuit breaker compatibility tabbypurr@gmail.com - 2017-03-16 10:12 -0700
                              Re: Very slightly OT: Circuit breaker compatibility krw@notreal.com - 2017-03-14 20:47 -0400
                            Re: Very slightly OT: Circuit breaker compatibility krw@notreal.com - 2017-03-14 20:47 -0400
                              Re: Very slightly OT: Circuit breaker compatibility Joerg <news@analogconsultants.com> - 2017-03-16 08:06 -0700
                          Re: Very slightly OT: Circuit breaker compatibility "Michael A. Terrell" <mike.terrell@earthlink.net> - 2017-03-17 16:29 -0400
                            Re: Very slightly OT: Circuit breaker compatibility krw@notreal.com - 2017-03-17 22:39 -0400
                              Re: Very slightly OT: Circuit breaker compatibility tabbypurr@gmail.com - 2017-03-18 01:52 -0700
                                Re: Very slightly OT: Circuit breaker compatibility krw@notreal.com - 2017-03-18 09:45 -0400
                                  Re: Very slightly OT: Circuit breaker compatibility tabbypurr@gmail.com - 2017-03-18 07:37 -0700
                                    Re: Very slightly OT: Circuit breaker compatibility krw@notreal.com - 2017-03-18 10:48 -0400
                                      Re: Very slightly OT: Circuit breaker compatibility tabbypurr@gmail.com - 2017-03-18 09:18 -0700
                                        Re: Very slightly OT: Circuit breaker compatibility krw@notreal.com - 2017-03-18 14:13 -0400
                                          Re: Very slightly OT: Circuit breaker compatibility tabbypurr@gmail.com - 2017-03-18 13:20 -0700
                                            Re: Very slightly OT: Circuit breaker compatibility krw@notreal.com - 2017-03-18 20:00 -0400
                                              Re: Very slightly OT: Circuit breaker compatibility tabbypurr@gmail.com - 2017-03-18 18:40 -0700
                                                Re: Very slightly OT: Circuit breaker compatibility krw@notreal.com - 2017-03-18 22:17 -0400
                              Re: Very slightly OT: Circuit breaker compatibility "Michael A. Terrell" <mike.terrell@earthlink.net> - 2017-03-19 12:14 -0400
      ) Spehro Pefhany <speffSNIP@interlogDOTyou.knowwhat> - 2017-03-12 01:12 -0500
        Re: ) tabbypurr@gmail.com - 2017-03-12 03:51 -0700
    Re: Very slightly OT: Circuit breaker compatibility Tim Wescott <tim@seemywebsite.really> - 2017-03-11 14:27 -0600
      Re: Very slightly OT: Circuit breaker compatibility Joerg <news@analogconsultants.com> - 2017-03-11 12:38 -0800
        Re: Very slightly OT: Circuit breaker compatibility Chris Jones <lugnut808@spam.yahoo.com> - 2017-03-12 23:57 +1100
          Re: Very slightly OT: Circuit breaker compatibility Joerg <news@analogconsultants.com> - 2017-03-12 07:17 -0700
    Re: Very slightly OT: Circuit breaker compatibility Jon Elson <elson@pico-systems.com> - 2017-03-11 20:14 -0600

Page 4 of 5 — ← Prev page 1 2 3 [4] 5  Next page →


#451829

FromLasse Langwadt Christensen <langwadt@fonz.dk>
Date2017-03-14 14:01 -0700
Message-ID<005da81f-171f-4b2a-88ad-65af0abf7bd1@googlegroups.com>
In reply to#451800
Den tirsdag den 14. marts 2017 kl. 19.57.47 UTC+1 skrev Joerg:
> On 2017-03-14 09:51, krw@notreal.com wrote:
> > On Tue, 14 Mar 2017 07:59:32 -0700, Joerg <news@analogconsultants.com>
> > wrote:
> >
> >> On 2017-03-14 06:40, tabbypurr@gmail.com wrote:
> >>> On Monday, 13 March 2017 22:49:13 UTC, Joerg  wrote:
> >>>> On 2017-03-12 11:38, tabbypurr wrote:
> >>>>> On Sunday, 12 March 2017 14:14:07 UTC, Joerg  wrote:
> >>>>>
> >>>>>>>> I found a whole slew of those. However, you also see
> >>>>>>>> breakers like that at yard sales and typically their
> >>>>>>>> contacting screws are rusted shut. The material quality
> >>>>>>>> wasn't all that great. That also was the case for all the
> >>>>>>>> breakers I tore out of this panel. I had to snip the wires
> >>>>>>>> as there was no way to loosen those screws one more time.
> >>>>>>>>
> >>>>>>>
> >>>>>>> http://www.ebay.com/itm/190797335710
> >>>>>>>
> >>>>>>
> >>>>>> Provided they did not store it in the basement, attic or garage
> >>>>>> for 30 years. In the verious listings nearly none of the photos
> >>>>>> shows the screw terminal. That's the part that rusts out and
> >>>>>> makes a breaker de-facto unusable. That is what ruined all the
> >>>>>> ones in the panel I was dealing with (non-heated room), even
> >>>>>> one that was never used.
> >>>>>
> >>>>> sand/file/grind some rust off & solder to it.
> >>>>>
> >>>>
> >>>> And then Monsieur L'Inspecteur waltzes in. One guy around here
> >>>> soldered connections in his house wiring which IMHO made it much
> >>>> safer than the usual fare. However, the inspector blew a gasket and
> >>>> made him rip it all out.
> >>>
> >>> Soldered connections aren't necessarily safer, it depends. It's easy
> >>> to inadequately mechanically support a soldered joint making it
> >>> fragile & thus unsafe. It also can melt, raising resistance under
> >>> adverse conditions. If you're an EE you oughta be able to do it
> >>> properly though.
> >
> > No, the real reason it isn't allowed is that it hasn't been "listed"
> > as an acceptable method.
> >>
> >> Yes, and if properly soldered and kept from moving they sure last longer
> >> than those dreaded wire nuts. I can't even count anymore how many times
> >> I opened a box and one of more of the wire nuts almost fell off. I've
> >> also see my share of wire nuts where the plastic cover had clearly melted.
> >
> > Wire nuts are perfectly safe if the installer has half a brain.  Of
> > the billions in service, how many have failed?
> >
> 
> I haven't kept count but my estimate would be more than 1% of the 
> connections I came across. All by licensed electricians though that 
> doesn't always mean much.
> 
> It only takes one wire nut coming loose ever so slightly to trigger a 
> house fire.

wire nuts and supposedly licensed electricians wrapping stuff in tape, 
just makes me cringe. That wouldn't fly here

[toc] | [prev] | [next] | [standalone]


#451833

FromJoerg <news@analogconsultants.com>
Date2017-03-14 14:21 -0700
Message-ID<eir57hFj9lnU2@mid.individual.net>
In reply to#451829
On 2017-03-14 14:01, Lasse Langwadt Christensen wrote:
> Den tirsdag den 14. marts 2017 kl. 19.57.47 UTC+1 skrev Joerg:
>> On 2017-03-14 09:51, krw@notreal.com wrote:
>>> On Tue, 14 Mar 2017 07:59:32 -0700, Joerg <news@analogconsultants.com>
>>> wrote:

[...]

>>>> Yes, and if properly soldered and kept from moving they sure last longer
>>>> than those dreaded wire nuts. I can't even count anymore how many times
>>>> I opened a box and one of more of the wire nuts almost fell off. I've
>>>> also see my share of wire nuts where the plastic cover had clearly melted.
>>>
>>> Wire nuts are perfectly safe if the installer has half a brain.  Of
>>> the billions in service, how many have failed?
>>>
>>
>> I haven't kept count but my estimate would be more than 1% of the
>> connections I came across. All by licensed electricians though that
>> doesn't always mean much.
>>
>> It only takes one wire nut coming loose ever so slightly to trigger a
>> house fire.
>
> wire nuts and supposedly licensed electricians wrapping stuff in tape,
> just makes me cringe. That wouldn't fly here
>

Yeah, when I moved across the pond and opened such a box for the first 
time I stood there with my jaw dropped. Couldn't believe it. But what I 
saw a week ago really took the cake.

-- 
Regards, Joerg

http://www.analogconsultants.com/

[toc] | [prev] | [next] | [standalone]


#451851

Fromtabbypurr@gmail.com
Date2017-03-14 16:59 -0700
Message-ID<89072712-6255-4835-b578-761eb1f03b1a@googlegroups.com>
In reply to#451833
On Tuesday, 14 March 2017 21:21:58 UTC, Joerg  wrote:
> On 2017-03-14 14:01, Lasse Langwadt Christensen wrote:
> > Den tirsdag den 14. marts 2017 kl. 19.57.47 UTC+1 skrev Joerg:
> >> On 2017-03-14 09:51, krw@notreal.com wrote:
> >>> On Tue, 14 Mar 2017 07:59:32 -0700, Joerg <news@analogconsultants.com>
> >>> wrote:
> 
> [...]
> 
> >>>> Yes, and if properly soldered and kept from moving they sure last longer
> >>>> than those dreaded wire nuts. I can't even count anymore how many times
> >>>> I opened a box and one of more of the wire nuts almost fell off. I've
> >>>> also see my share of wire nuts where the plastic cover had clearly melted.
> >>>
> >>> Wire nuts are perfectly safe if the installer has half a brain.  Of
> >>> the billions in service, how many have failed?
> >>>
> >>
> >> I haven't kept count but my estimate would be more than 1% of the
> >> connections I came across. All by licensed electricians though that
> >> doesn't always mean much.
> >>
> >> It only takes one wire nut coming loose ever so slightly to trigger a
> >> house fire.
> >
> > wire nuts and supposedly licensed electricians wrapping stuff in tape,
> > just makes me cringe. That wouldn't fly here
> >
> 
> Yeah, when I moved across the pond and opened such a box for the first 
> time I stood there with my jaw dropped. Couldn't believe it. But what I 
> saw a week ago really took the cake.

Wire nuts were banned here in the 1950s (UK). But now we have push-in sprung connectors eg Wago, which are worse, as well as the traditional choc-block ones.

Connector types tested to destruction:
https://www.youtube.com/watch?v=2uYD8e7idnY


NT

[toc] | [prev] | [next] | [standalone]


#451939

FromChris Jones <lugnut808@spam.yahoo.com>
Date2017-03-16 00:50 +1100
Message-ID<MEbyA.262260$jg2.258877@fx11.fr7>
In reply to#451851
On 15/03/2017 10:59, tabbypurr@gmail.com wrote:
> On Tuesday, 14 March 2017 21:21:58 UTC, Joerg  wrote:
>> On 2017-03-14 14:01, Lasse Langwadt Christensen wrote:
>>> Den tirsdag den 14. marts 2017 kl. 19.57.47 UTC+1 skrev Joerg:
>>>> On 2017-03-14 09:51, krw@notreal.com wrote:
>>>>> On Tue, 14 Mar 2017 07:59:32 -0700, Joerg <news@analogconsultants.com>
>>>>> wrote:
>>
>> [...]
>>
>>>>>> Yes, and if properly soldered and kept from moving they sure last longer
>>>>>> than those dreaded wire nuts. I can't even count anymore how many times
>>>>>> I opened a box and one of more of the wire nuts almost fell off. I've
>>>>>> also see my share of wire nuts where the plastic cover had clearly melted.
>>>>>
>>>>> Wire nuts are perfectly safe if the installer has half a brain.  Of
>>>>> the billions in service, how many have failed?
>>>>>
>>>>
>>>> I haven't kept count but my estimate would be more than 1% of the
>>>> connections I came across. All by licensed electricians though that
>>>> doesn't always mean much.
>>>>
>>>> It only takes one wire nut coming loose ever so slightly to trigger a
>>>> house fire.
>>>
>>> wire nuts and supposedly licensed electricians wrapping stuff in tape,
>>> just makes me cringe. That wouldn't fly here
>>>
>>
>> Yeah, when I moved across the pond and opened such a box for the first
>> time I stood there with my jaw dropped. Couldn't believe it. But what I
>> saw a week ago really took the cake.
>
> Wire nuts were banned here in the 1950s (UK). But now we have push-in sprung connectors eg Wago, which are worse, as well as the traditional choc-block ones.

What don't you like about Wago connectors? (apart from the price)

[toc] | [prev] | [next] | [standalone]


#451944

Fromtabbypurr@gmail.com
Date2017-03-15 07:26 -0700
Message-ID<dccd4580-7d39-4417-af43-9d6844b24d19@googlegroups.com>
In reply to#451939
On Wednesday, 15 March 2017 13:50:40 UTC, Chris Jones  wrote:
> On 15/03/2017 10:59, tabbypurr wrote:
> > On Tuesday, 14 March 2017 21:21:58 UTC, Joerg  wrote:
> >> On 2017-03-14 14:01, Lasse Langwadt Christensen wrote:
> >>> Den tirsdag den 14. marts 2017 kl. 19.57.47 UTC+1 skrev Joerg:
> >>>> On 2017-03-14 09:51, krw@notreal.com wrote:
> >>>>> On Tue, 14 Mar 2017 07:59:32 -0700, Joerg <news@analogconsultants.com>
> >>>>> wrote:
> >>
> >> [...]
> >>
> >>>>>> Yes, and if properly soldered and kept from moving they sure last longer
> >>>>>> than those dreaded wire nuts. I can't even count anymore how many times
> >>>>>> I opened a box and one of more of the wire nuts almost fell off. I've
> >>>>>> also see my share of wire nuts where the plastic cover had clearly melted.
> >>>>>
> >>>>> Wire nuts are perfectly safe if the installer has half a brain.  Of
> >>>>> the billions in service, how many have failed?
> >>>>>
> >>>>
> >>>> I haven't kept count but my estimate would be more than 1% of the
> >>>> connections I came across. All by licensed electricians though that
> >>>> doesn't always mean much.
> >>>>
> >>>> It only takes one wire nut coming loose ever so slightly to trigger a
> >>>> house fire.
> >>>
> >>> wire nuts and supposedly licensed electricians wrapping stuff in tape,
> >>> just makes me cringe. That wouldn't fly here
> >>>
> >>
> >> Yeah, when I moved across the pond and opened such a box for the first
> >> time I stood there with my jaw dropped. Couldn't believe it. But what I
> >> saw a week ago really took the cake.
> >
> > Wire nuts were banned here in the 1950s (UK). But now we have push-in sprung connectors eg Wago, which are worse, as well as the traditional choc-block ones.
> 
> What don't you like about Wago connectors? (apart from the price)

Poor contact area. Poor grip on the wire. And in the overload test they were the only type to fail, producing smoke & fire before the others.


NT

[toc] | [prev] | [next] | [standalone]


#451982

FromLasse Langwadt Christensen <langwadt@fonz.dk>
Date2017-03-15 11:17 -0700
Message-ID<d1930ca7-cd85-4f62-98b7-c5e20b5fa764@googlegroups.com>
In reply to#451944
Den onsdag den 15. marts 2017 kl. 15.27.07 UTC+1 skrev tabb...@gmail.com:
> On Wednesday, 15 March 2017 13:50:40 UTC, Chris Jones  wrote:
> > On 15/03/2017 10:59, tabbypurr wrote:
> > > On Tuesday, 14 March 2017 21:21:58 UTC, Joerg  wrote:
> > >> On 2017-03-14 14:01, Lasse Langwadt Christensen wrote:
> > >>> Den tirsdag den 14. marts 2017 kl. 19.57.47 UTC+1 skrev Joerg:
> > >>>> On 2017-03-14 09:51, krw@notreal.com wrote:
> > >>>>> On Tue, 14 Mar 2017 07:59:32 -0700, Joerg <news@analogconsultants.com>
> > >>>>> wrote:
> > >>
> > >> [...]
> > >>
> > >>>>>> Yes, and if properly soldered and kept from moving they sure last longer
> > >>>>>> than those dreaded wire nuts. I can't even count anymore how many times
> > >>>>>> I opened a box and one of more of the wire nuts almost fell off. I've
> > >>>>>> also see my share of wire nuts where the plastic cover had clearly melted.
> > >>>>>
> > >>>>> Wire nuts are perfectly safe if the installer has half a brain.  Of
> > >>>>> the billions in service, how many have failed?
> > >>>>>
> > >>>>
> > >>>> I haven't kept count but my estimate would be more than 1% of the
> > >>>> connections I came across. All by licensed electricians though that
> > >>>> doesn't always mean much.
> > >>>>
> > >>>> It only takes one wire nut coming loose ever so slightly to trigger a
> > >>>> house fire.
> > >>>
> > >>> wire nuts and supposedly licensed electricians wrapping stuff in tape,
> > >>> just makes me cringe. That wouldn't fly here
> > >>>
> > >>
> > >> Yeah, when I moved across the pond and opened such a box for the first
> > >> time I stood there with my jaw dropped. Couldn't believe it. But what I
> > >> saw a week ago really took the cake.
> > >
> > > Wire nuts were banned here in the 1950s (UK). But now we have push-in sprung connectors eg Wago, which are worse, as well as the traditional choc-block ones.
> > 
> > What don't you like about Wago connectors? (apart from the price)
> 
> Poor contact area. Poor grip on the wire. And in the overload test they were the only type to fail, producing smoke & fire before the others.


yeh, if you replace you fuse with a nail then shortly after the wires have
caught fire and burned the house down, the wago connector might smoke a bit

and it didn't fail, the wire failed, probably because it had been nicked when removing the insulation 

[toc] | [prev] | [next] | [standalone]


#452025

Fromtabbypurr@gmail.com
Date2017-03-15 16:31 -0700
Message-ID<48c0af49-e45a-480a-9284-f45ecb4c0670@googlegroups.com>
In reply to#451982
On Wednesday, 15 March 2017 18:17:47 UTC, Lasse Langwadt Christensen  wrote:
> Den onsdag den 15. marts 2017 kl. 15.27.07 UTC+1 skrev tabb...@gmail.com:
> > On Wednesday, 15 March 2017 13:50:40 UTC, Chris Jones  wrote:
> > > On 15/03/2017 10:59, tabbypurr wrote:

> > > > Wire nuts were banned here in the 1950s (UK). But now we have push-in sprung connectors eg Wago, which are worse, as well as the traditional choc-block ones.
> > > 
> > > What don't you like about Wago connectors? (apart from the price)
> > 
> > Poor contact area. Poor grip on the wire. And in the overload test they were the only type to fail, producing smoke & fire before the others.
> 
> 
> yeh, if you replace you fuse with a nail then shortly after the wires have
> caught fire and burned the house down, the wago connector might smoke a bit

In reality there are 69,000 domestic fires a year in UK killing 486 people (2001). So I don't want my electrical connections to be so flimsy that they don't even have a proper hold on the cable. What you saw in that test was new connections. 20 years later stuff gets oxidised if it's not gas-tight. Now I might be wrong but that Wago did not look in any way gas-tight to me.

> and it didn't fail, the wire failed, probably because it had been nicked when removing the insulation

The Wago did fail, and before anything else did. I count catching fire as failing. Use them if you want, I don't.


NT

[toc] | [prev] | [next] | [standalone]


#452029

FromLasse Langwadt Christensen <langwadt@fonz.dk>
Date2017-03-15 16:59 -0700
Message-ID<a01cee46-502c-4af9-b11e-38f5f53f68ac@googlegroups.com>
In reply to#452025
Den torsdag den 16. marts 2017 kl. 00.31.24 UTC+1 skrev tabb...@gmail.com:
> On Wednesday, 15 March 2017 18:17:47 UTC, Lasse Langwadt Christensen  wrote:
> > Den onsdag den 15. marts 2017 kl. 15.27.07 UTC+1 skrev tabb...@gmail.com:
> > > On Wednesday, 15 March 2017 13:50:40 UTC, Chris Jones  wrote:
> > > > On 15/03/2017 10:59, tabbypurr wrote:
> 
> > > > > Wire nuts were banned here in the 1950s (UK). But now we have push-in sprung connectors eg Wago, which are worse, as well as the traditional choc-block ones.
> > > > 
> > > > What don't you like about Wago connectors? (apart from the price)
> > > 
> > > Poor contact area. Poor grip on the wire. And in the overload test they were the only type to fail, producing smoke & fire before the others.
> > 
> > 
> > yeh, if you replace you fuse with a nail then shortly after the wires have
> > caught fire and burned the house down, the wago connector might smoke a bit
> 
> In reality there are 69,000 domestic fires a year in UK killing 486 people (2001). So I don't want my electrical connections to be so flimsy that they don't even have a proper hold on the cable. What you saw in that test was new connections. 20 years later stuff gets oxidised if it's not gas-tight. Now I might be wrong but that Wago did not look in any way gas-tight to me.
> 
> > and it didn't fail, the wire failed, probably because it had been nicked when removing the insulation
> 
> The Wago did fail, and before anything else did. I count catching fire as failing. Use them if you want, I don't.
> 

what video did you watch? after several minutes of 70A and the wire burned 
to a crisp the wire failed

[toc] | [prev] | [next] | [standalone]


#452057

Fromtabbypurr@gmail.com
Date2017-03-15 19:06 -0700
Message-ID<d2627aaf-5724-4acf-8151-370af48d7463@googlegroups.com>
In reply to#452029
On Wednesday, 15 March 2017 23:59:33 UTC, Lasse Langwadt Christensen  wrote:
> Den torsdag den 16. marts 2017 kl. 00.31.24 UTC+1 skrev tabby:
> > On Wednesday, 15 March 2017 18:17:47 UTC, Lasse Langwadt Christensen  wrote:
> > > Den onsdag den 15. marts 2017 kl. 15.27.07 UTC+1 skrev tabb...@gmail.com:
> > > > On Wednesday, 15 March 2017 13:50:40 UTC, Chris Jones  wrote:
> > > > > On 15/03/2017 10:59, tabbypurr wrote:
> > 
> > > > > > Wire nuts were banned here in the 1950s (UK). But now we have push-in sprung connectors eg Wago, which are worse, as well as the traditional choc-block ones.
> > > > > 
> > > > > What don't you like about Wago connectors? (apart from the price)
> > > > 
> > > > Poor contact area. Poor grip on the wire. And in the overload test they were the only type to fail, producing smoke & fire before the others.
> > > 
> > > 
> > > yeh, if you replace you fuse with a nail then shortly after the wires have
> > > caught fire and burned the house down, the wago connector might smoke a bit
> > 
> > In reality there are 69,000 domestic fires a year in UK killing 486 people (2001). So I don't want my electrical connections to be so flimsy that they don't even have a proper hold on the cable. What you saw in that test was new connections. 20 years later stuff gets oxidised if it's not gas-tight. Now I might be wrong but that Wago did not look in any way gas-tight to me.
> > 
> > > and it didn't fail, the wire failed, probably because it had been nicked when removing the insulation
> > 
> > The Wago did fail, and before anything else did. I count catching fire as failing. Use them if you want, I don't.
> > 
> 
> what video did you watch? after several minutes of 70A and the wire burned 
> to a crisp the wire failed

https://www.youtube.com/watch?v=2uYD8e7idnY


NT

[toc] | [prev] | [next] | [standalone]


#452104

FromChris Jones <lugnut808@spam.yahoo.com>
Date2017-03-16 23:26 +1100
Message-ID<dwvyA.368413$w46.301708@fx39.am4>
In reply to#452057
On 16/03/2017 13:06, tabbypurr@gmail.com wrote:
> On Wednesday, 15 March 2017 23:59:33 UTC, Lasse Langwadt Christensen  wrote:
>> Den torsdag den 16. marts 2017 kl. 00.31.24 UTC+1 skrev tabby:
>>> On Wednesday, 15 March 2017 18:17:47 UTC, Lasse Langwadt Christensen  wrote:
>>>> Den onsdag den 15. marts 2017 kl. 15.27.07 UTC+1 skrev tabb...@gmail.com:
>>>>> On Wednesday, 15 March 2017 13:50:40 UTC, Chris Jones  wrote:
>>>>>> On 15/03/2017 10:59, tabbypurr wrote:
>>>
>>>>>>> Wire nuts were banned here in the 1950s (UK). But now we have push-in sprung connectors eg Wago, which are worse, as well as the traditional choc-block ones.
>>>>>>
>>>>>> What don't you like about Wago connectors? (apart from the price)
>>>>>
>>>>> Poor contact area. Poor grip on the wire. And in the overload test they were the only type to fail, producing smoke & fire before the others.
>>>>
>>>>
>>>> yeh, if you replace you fuse with a nail then shortly after the wires have
>>>> caught fire and burned the house down, the wago connector might smoke a bit
>>>
>>> In reality there are 69,000 domestic fires a year in UK killing 486 people (2001). So I don't want my electrical connections to be so flimsy that they don't even have a proper hold on the cable. What you saw in that test was new connections. 20 years later stuff gets oxidised if it's not gas-tight. Now I might be wrong but that Wago did not look in any way gas-tight to me.
>>>
>>>> and it didn't fail, the wire failed, probably because it had been nicked when removing the insulation
>>>
>>> The Wago did fail, and before anything else did. I count catching fire as failing. Use them if you want, I don't.
>>>
>>
>> what video did you watch? after several minutes of 70A and the wire burned
>> to a crisp the wire failed
>
> https://www.youtube.com/watch?v=2uYD8e7idnY
>
>
> NT
>

If the wire has already burnt off its insulation, probably shorted to 
its neighbours and set fire to my house, I won't mind too much if the 
Wago connector also burns after that. The solution to the problem is to 
install a proper circuit breaker, to prevent 70A from flowing through 
that wire.

I really don't see much need for the connector to be safe at currents 
higher than what would make the wire itself dangerous, and higher than 
the current that would trip the circuit breaker. Similarly, I don't see 
much point in making the door of the house from 2 inch thick steel 
plate, if the adjacent wall is just made from plasterboard and wood.

I have had the situation of electricians forgetting to tighten screw 
connectors so the wire pretty much fell out, and that could cause 
overheating at currents that would not trip the circuit breaker. That 
problem could not occur with the Wago connector. It would be interesting 
to get some real statistics about the rate of electical fires resulting 
from different types of connectors.

[toc] | [prev] | [next] | [standalone]


#452140

Fromtabbypurr@gmail.com
Date2017-03-16 10:12 -0700
Message-ID<de113815-a832-4bf2-a8d5-3b5950957916@googlegroups.com>
In reply to#452104
On Thursday, 16 March 2017 12:26:59 UTC, Chris Jones  wrote:
> On 16/03/2017 13:06, tabbypurr wrote:
> > On Wednesday, 15 March 2017 23:59:33 UTC, Lasse Langwadt Christensen  wrote:
> >> Den torsdag den 16. marts 2017 kl. 00.31.24 UTC+1 skrev tabby:
> >>> On Wednesday, 15 March 2017 18:17:47 UTC, Lasse Langwadt Christensen  wrote:
> >>>> Den onsdag den 15. marts 2017 kl. 15.27.07 UTC+1 skrev tabb...@gmail.com:
> >>>>> On Wednesday, 15 March 2017 13:50:40 UTC, Chris Jones  wrote:
> >>>>>> On 15/03/2017 10:59, tabbypurr wrote:
> >>>
> >>>>>>> Wire nuts were banned here in the 1950s (UK). But now we have push-in sprung connectors eg Wago, which are worse, as well as the traditional choc-block ones.
> >>>>>>
> >>>>>> What don't you like about Wago connectors? (apart from the price)
> >>>>>
> >>>>> Poor contact area. Poor grip on the wire. And in the overload test they were the only type to fail, producing smoke & fire before the others.
> >>>>
> >>>>
> >>>> yeh, if you replace you fuse with a nail then shortly after the wires have
> >>>> caught fire and burned the house down, the wago connector might smoke a bit
> >>>
> >>> In reality there are 69,000 domestic fires a year in UK killing 486 people (2001). So I don't want my electrical connections to be so flimsy that they don't even have a proper hold on the cable. What you saw in that test was new connections. 20 years later stuff gets oxidised if it's not gas-tight. Now I might be wrong but that Wago did not look in any way gas-tight to me.
> >>>
> >>>> and it didn't fail, the wire failed, probably because it had been nicked when removing the insulation
> >>>
> >>> The Wago did fail, and before anything else did. I count catching fire as failing. Use them if you want, I don't.
> >>>
> >>
> >> what video did you watch? after several minutes of 70A and the wire burned
> >> to a crisp the wire failed
> >
> > https://www.youtube.com/watch?v=2uYD8e7idnY
> >
> >
> > NT
> >
> 
> If the wire has already burnt off its insulation, probably shorted to 
> its neighbours and set fire to my house, I won't mind too much if the 
> Wago connector also burns after that. The solution to the problem is to 
> install a proper circuit breaker, to prevent 70A from flowing through 
> that wire.
> 
> I really don't see much need for the connector to be safe at currents 
> higher than what would make the wire itself dangerous, and higher than 
> the current that would trip the circuit breaker. Similarly, I don't see 
> much point in making the door of the house from 2 inch thick steel 
> plate, if the adjacent wall is just made from plasterboard and wood.
> 
> I have had the situation of electricians forgetting to tighten screw 
> connectors so the wire pretty much fell out, and that could cause 
> overheating at currents that would not trip the circuit breaker. That 
> problem could not occur with the Wago connector. It would be interesting 
> to get some real statistics about the rate of electical fires resulting 
> from different types of connectors.

It would indeed. Hopefully some day all known causes will be recorded & the risks calculated.


NT

[toc] | [prev] | [next] | [standalone]


#451869

Fromkrw@notreal.com
Date2017-03-14 20:47 -0400
Message-ID<1p3hcc9adpdetq8ubpnustfvtnakij6gv9@4ax.com>
In reply to#451829
On Tue, 14 Mar 2017 14:01:31 -0700 (PDT), Lasse Langwadt Christensen
<langwadt@fonz.dk> wrote:

>Den tirsdag den 14. marts 2017 kl. 19.57.47 UTC+1 skrev Joerg:
>> On 2017-03-14 09:51, krw@notreal.com wrote:
>> > On Tue, 14 Mar 2017 07:59:32 -0700, Joerg <news@analogconsultants.com>
>> > wrote:
>> >
>> >> On 2017-03-14 06:40, tabbypurr@gmail.com wrote:
>> >>> On Monday, 13 March 2017 22:49:13 UTC, Joerg  wrote:
>> >>>> On 2017-03-12 11:38, tabbypurr wrote:
>> >>>>> On Sunday, 12 March 2017 14:14:07 UTC, Joerg  wrote:
>> >>>>>
>> >>>>>>>> I found a whole slew of those. However, you also see
>> >>>>>>>> breakers like that at yard sales and typically their
>> >>>>>>>> contacting screws are rusted shut. The material quality
>> >>>>>>>> wasn't all that great. That also was the case for all the
>> >>>>>>>> breakers I tore out of this panel. I had to snip the wires
>> >>>>>>>> as there was no way to loosen those screws one more time.
>> >>>>>>>>
>> >>>>>>>
>> >>>>>>> http://www.ebay.com/itm/190797335710
>> >>>>>>>
>> >>>>>>
>> >>>>>> Provided they did not store it in the basement, attic or garage
>> >>>>>> for 30 years. In the verious listings nearly none of the photos
>> >>>>>> shows the screw terminal. That's the part that rusts out and
>> >>>>>> makes a breaker de-facto unusable. That is what ruined all the
>> >>>>>> ones in the panel I was dealing with (non-heated room), even
>> >>>>>> one that was never used.
>> >>>>>
>> >>>>> sand/file/grind some rust off & solder to it.
>> >>>>>
>> >>>>
>> >>>> And then Monsieur L'Inspecteur waltzes in. One guy around here
>> >>>> soldered connections in his house wiring which IMHO made it much
>> >>>> safer than the usual fare. However, the inspector blew a gasket and
>> >>>> made him rip it all out.
>> >>>
>> >>> Soldered connections aren't necessarily safer, it depends. It's easy
>> >>> to inadequately mechanically support a soldered joint making it
>> >>> fragile & thus unsafe. It also can melt, raising resistance under
>> >>> adverse conditions. If you're an EE you oughta be able to do it
>> >>> properly though.
>> >
>> > No, the real reason it isn't allowed is that it hasn't been "listed"
>> > as an acceptable method.
>> >>
>> >> Yes, and if properly soldered and kept from moving they sure last longer
>> >> than those dreaded wire nuts. I can't even count anymore how many times
>> >> I opened a box and one of more of the wire nuts almost fell off. I've
>> >> also see my share of wire nuts where the plastic cover had clearly melted.
>> >
>> > Wire nuts are perfectly safe if the installer has half a brain.  Of
>> > the billions in service, how many have failed?
>> >
>> 
>> I haven't kept count but my estimate would be more than 1% of the 
>> connections I came across. All by licensed electricians though that 
>> doesn't always mean much.
>> 
>> It only takes one wire nut coming loose ever so slightly to trigger a 
>> house fire.
>
>wire nuts and supposedly licensed electricians wrapping stuff in tape, 
>just makes me cringe. That wouldn't fly here
>
Wire nuts are perfectly good.  Tape is nuts.  

[toc] | [prev] | [next] | [standalone]


#451868

Fromkrw@notreal.com
Date2017-03-14 20:47 -0400
Message-ID<lj3hccdme2npjt2sd1upm7uancor8tbiqb@4ax.com>
In reply to#451800
On Tue, 14 Mar 2017 11:57:45 -0700, Joerg <news@analogconsultants.com>
wrote:

>On 2017-03-14 09:51, krw@notreal.com wrote:
>> On Tue, 14 Mar 2017 07:59:32 -0700, Joerg <news@analogconsultants.com>
>> wrote:
>>
>>> On 2017-03-14 06:40, tabbypurr@gmail.com wrote:
>>>> On Monday, 13 March 2017 22:49:13 UTC, Joerg  wrote:
>>>>> On 2017-03-12 11:38, tabbypurr wrote:
>>>>>> On Sunday, 12 March 2017 14:14:07 UTC, Joerg  wrote:
>>>>>>
>>>>>>>>> I found a whole slew of those. However, you also see
>>>>>>>>> breakers like that at yard sales and typically their
>>>>>>>>> contacting screws are rusted shut. The material quality
>>>>>>>>> wasn't all that great. That also was the case for all the
>>>>>>>>> breakers I tore out of this panel. I had to snip the wires
>>>>>>>>> as there was no way to loosen those screws one more time.
>>>>>>>>>
>>>>>>>>
>>>>>>>> http://www.ebay.com/itm/190797335710
>>>>>>>>
>>>>>>>
>>>>>>> Provided they did not store it in the basement, attic or garage
>>>>>>> for 30 years. In the verious listings nearly none of the photos
>>>>>>> shows the screw terminal. That's the part that rusts out and
>>>>>>> makes a breaker de-facto unusable. That is what ruined all the
>>>>>>> ones in the panel I was dealing with (non-heated room), even
>>>>>>> one that was never used.
>>>>>>
>>>>>> sand/file/grind some rust off & solder to it.
>>>>>>
>>>>>
>>>>> And then Monsieur L'Inspecteur waltzes in. One guy around here
>>>>> soldered connections in his house wiring which IMHO made it much
>>>>> safer than the usual fare. However, the inspector blew a gasket and
>>>>> made him rip it all out.
>>>>
>>>> Soldered connections aren't necessarily safer, it depends. It's easy
>>>> to inadequately mechanically support a soldered joint making it
>>>> fragile & thus unsafe. It also can melt, raising resistance under
>>>> adverse conditions. If you're an EE you oughta be able to do it
>>>> properly though.
>>
>> No, the real reason it isn't allowed is that it hasn't been "listed"
>> as an acceptable method.
>>>
>>> Yes, and if properly soldered and kept from moving they sure last longer
>>> than those dreaded wire nuts. I can't even count anymore how many times
>>> I opened a box and one of more of the wire nuts almost fell off. I've
>>> also see my share of wire nuts where the plastic cover had clearly melted.
>>
>> Wire nuts are perfectly safe if the installer has half a brain.  Of
>> the billions in service, how many have failed?
>>
>
>I haven't kept count but my estimate would be more than 1% of the 
>connections I came across. All by licensed electricians though that 
>doesn't always mean much.

Of course, you only tend to look at problematic circuits.  For the
record, Iv'e never found one bad one.  Some were loose but the wires
were still quite tightly wrapped (that's the point anyway).

>
>It only takes one wire nut coming loose ever so slightly to trigger a 
>house fire.

Utter nonsense.  The wire nut is not supposed to be the connection. If
what you say were true, houses would never last a year without
spontaneously combusting.

[toc] | [prev] | [next] | [standalone]


#452113

FromJoerg <news@analogconsultants.com>
Date2017-03-16 08:06 -0700
Message-ID<eivnuoFgafjU3@mid.individual.net>
In reply to#451868
On 2017-03-14 17:47, krw@notreal.com wrote:

[...]

>>
>> It only takes one wire nut coming loose ever so slightly to trigger a
>> house fire.
>
> Utter nonsense.  The wire nut is not supposed to be the connection. If
> what you say were true, houses would never last a year without
> spontaneously combusting.
>

https://dengarden.com/home-improvement/What-Causes-Electrical-Fires-in-the-Home

-- 
Regards, Joerg

http://www.analogconsultants.com/

[toc] | [prev] | [next] | [standalone]


#452321

From"Michael A. Terrell" <mike.terrell@earthlink.net>
Date2017-03-17 16:29 -0400
Message-ID<M9ydnTRLAfup2lHFnZ2dnUU7-bednZ2d@earthlink.com>
In reply to#451786
krw@notreal.com wrote:
>
> Wire nuts are perfectly safe if the installer has half a brain.  Of
> the billions in service, how many have failed?


    Wire nuts are legal on commercial fire alarms, so the insurance 
companies trust them.


-- 
Never piss off an Engineer!

They don't get mad.

They don't get even.

They go for over unity! ;-)

[toc] | [prev] | [next] | [standalone]


#452372

Fromkrw@notreal.com
Date2017-03-17 22:39 -0400
Message-ID<287pccd6gs2ilp253d8eis6rfe7q6q7tbk@4ax.com>
In reply to#452321
On Fri, 17 Mar 2017 16:29:41 -0400, "Michael A. Terrell"
<mike.terrell@earthlink.net> wrote:

>krw@notreal.com wrote:
>>
>> Wire nuts are perfectly safe if the installer has half a brain.  Of
>> the billions in service, how many have failed?
>
>
>    Wire nuts are legal on commercial fire alarms, so the insurance 
>companies trust them.

So do the fire underwriters (NEC) and they're pretty anal.

[toc] | [prev] | [next] | [standalone]


#452387

Fromtabbypurr@gmail.com
Date2017-03-18 01:52 -0700
Message-ID<3ba0bb2f-b84f-4fb7-bc81-5d79b0805fe1@googlegroups.com>
In reply to#452372
On Saturday, 18 March 2017 02:39:52 UTC, k...@notreal.com  wrote:
> On Fri, 17 Mar 2017 16:29:41 -0400, "Michael A. Terrell"
> <mike.terrell@earthlink.net> wrote:
> >krw@notreal.com wrote:
> >>
> >> Wire nuts are perfectly safe if the installer has half a brain.  Of
> >> the billions in service, how many have failed?
> >
> >
> >    Wire nuts are legal on commercial fire alarms, so the insurance 
> >companies trust them.
> 
> So do the fire underwriters (NEC) and they're pretty anal.

Unless you're talking about a different type to the one I know as wirenuts, they don't produce a gas-tight join, and are thus a reliability & safety risk. 

US mains plugs were tested in the UK years ago and given a rating of 50v 2.5A max. US mains electrics is illegal here on a list of safety grounds. Why Americans think their country is the best at everything no-one knows.


NT

[toc] | [prev] | [next] | [standalone]


#452415

Fromkrw@notreal.com
Date2017-03-18 09:45 -0400
Message-ID<saeqccp1rg8orvshs6rtiaud316ipnmqjp@4ax.com>
In reply to#452387
On Sat, 18 Mar 2017 01:52:57 -0700 (PDT), tabbypurr@gmail.com wrote:

>On Saturday, 18 March 2017 02:39:52 UTC, k...@notreal.com  wrote:
>> On Fri, 17 Mar 2017 16:29:41 -0400, "Michael A. Terrell"
>> <mike.terrell@earthlink.net> wrote:
>> >krw@notreal.com wrote:
>> >>
>> >> Wire nuts are perfectly safe if the installer has half a brain.  Of
>> >> the billions in service, how many have failed?
>> >
>> >
>> >    Wire nuts are legal on commercial fire alarms, so the insurance 
>> >companies trust them.
>> 
>> So do the fire underwriters (NEC) and they're pretty anal.
>
>Unless you're talking about a different type to the one I know as wirenuts, they don't produce a gas-tight join, and are thus a reliability & safety risk. 

Absurd.  A few billion in the field say otherwise.

>US mains plugs were tested in the UK years ago and given a rating of 50v 2.5A max. US mains electrics is illegal here on a list of safety grounds. Why Americans think their country is the best at everything no-one knows.

More pompous Brit absurdity.  A few billion say otherwise.

[toc] | [prev] | [next] | [standalone]


#452424

Fromtabbypurr@gmail.com
Date2017-03-18 07:37 -0700
Message-ID<944f0c8f-ed52-43ef-9e4f-c75862b178a1@googlegroups.com>
In reply to#452415
On Saturday, 18 March 2017 13:45:07 UTC, k...@notreal.com  wrote:
> On Sat, 18 Mar 2017 01:52:57 -0700 (PDT), tabbypurr wrote:
> >On Saturday, 18 March 2017 02:39:52 UTC, k...@notreal.com  wrote:
> >> On Fri, 17 Mar 2017 16:29:41 -0400, "Michael A. Terrell"
> >> <mike.terrell@earthlink.net> wrote:
> >> >krw@notreal.com wrote:
> >> >>
> >> >> Wire nuts are perfectly safe if the installer has half a brain.  Of
> >> >> the billions in service, how many have failed?
> >> >
> >> >
> >> >    Wire nuts are legal on commercial fire alarms, so the insurance 
> >> >companies trust them.
> >> 
> >> So do the fire underwriters (NEC) and they're pretty anal.
> >
> >Unless you're talking about a different type to the one I know as wirenuts, they don't produce a gas-tight join, and are thus a reliability & safety risk. 
> 
> Absurd.  A few billion in the field say otherwise.
> 
> >US mains plugs were tested in the UK years ago and given a rating of 50v 2.5A max. US mains electrics is illegal here on a list of safety grounds. Why Americans think their country is the best at everything no-one knows.
> 
> More pompous Brit absurdity.  A few billion say otherwise.

I think you'll find US rates of domestic electrical fires are worse than ours.

Failure of connections to be gas tight has long been known to result in greater fire risk.


NT

[toc] | [prev] | [next] | [standalone]


#452428

Fromkrw@notreal.com
Date2017-03-18 10:48 -0400
Message-ID<35iqcc59t65001pa2qosafpfv6h5slo2sf@4ax.com>
In reply to#452424
On Sat, 18 Mar 2017 07:37:30 -0700 (PDT), tabbypurr@gmail.com wrote:

>On Saturday, 18 March 2017 13:45:07 UTC, k...@notreal.com  wrote:
>> On Sat, 18 Mar 2017 01:52:57 -0700 (PDT), tabbypurr wrote:
>> >On Saturday, 18 March 2017 02:39:52 UTC, k...@notreal.com  wrote:
>> >> On Fri, 17 Mar 2017 16:29:41 -0400, "Michael A. Terrell"
>> >> <mike.terrell@earthlink.net> wrote:
>> >> >krw@notreal.com wrote:
>> >> >>
>> >> >> Wire nuts are perfectly safe if the installer has half a brain.  Of
>> >> >> the billions in service, how many have failed?
>> >> >
>> >> >
>> >> >    Wire nuts are legal on commercial fire alarms, so the insurance 
>> >> >companies trust them.
>> >> 
>> >> So do the fire underwriters (NEC) and they're pretty anal.
>> >
>> >Unless you're talking about a different type to the one I know as wirenuts, they don't produce a gas-tight join, and are thus a reliability & safety risk. 
>> 
>> Absurd.  A few billion in the field say otherwise.
>> 
>> >US mains plugs were tested in the UK years ago and given a rating of 50v 2.5A max. US mains electrics is illegal here on a list of safety grounds. Why Americans think their country is the best at everything no-one knows.
>> 
>> More pompous Brit absurdity.  A few billion say otherwise.
>
>I think you'll find US rates of domestic electrical fires are worse than ours.

Proving nothing, even if so.

>Failure of connections to be gas tight has long been known to result in greater fire risk.

Nonsense.

[toc] | [prev] | [next] | [standalone]