  Medical devices and US 220V electrics RBlack <news@rblack01.plus.com> - 2017-05-25 13:05 +0100
    Re: Medical devices and US 220V electrics Winfield Hill <hill@rowland.harvard.edu> - 2017-05-25 05:55 -0700
    Re: Medical devices and US 220V electrics upsidedown@downunder.com - 2017-05-25 17:26 +0300
      Re: Medical devices and US 220V electrics Phil Hobbs <pcdhSpamMeSenseless@electrooptical.net> - 2017-05-25 10:27 -0400
        Re: Medical devices and US 220V electrics George Herold <gherold@teachspin.com> - 2017-05-25 08:39 -0700
          Re: Medical devices and US 220V electrics krw@notreal.com - 2017-05-25 12:40 -0400
      Re: Medical devices and US 220V electrics Jan Panteltje <pNa0nStpealmtje@yahoo.com> - 2017-05-25 15:03 +0000
        Re: Medical devices and US 220V electrics upsidedown@downunder.com - 2017-05-25 20:09 +0300
      Re: Medical devices and US 220V electrics RBlack <news@rblack01.plus.com> - 2017-05-25 16:56 +0100
        Re: Medical devices and US 220V electrics Jan Panteltje <pNa0nStpealmtje@yahoo.com> - 2017-05-25 16:42 +0000
        Re: Medical devices and US 220V electrics upsidedown@downunder.com - 2017-05-25 20:38 +0300
        Re: Medical devices and US 220V electrics whit3rd <whit3rd@gmail.com> - 2017-05-25 10:48 -0700
        Re: Medical devices and US 220V electrics Neon John <no@never.com> - 2017-05-28 15:48 -0400
        Re: Medical devices and US 220V electrics rickman <gnuarm@gmail.com> - 2017-05-29 01:08 -0400
      Re: Medical devices and US 220V electrics Cursitor Doom <curd@notformail.com> - 2017-05-25 17:51 +0000
        Re: Medical devices and US 220V electrics upsidedown@downunder.com - 2017-05-25 21:25 +0300
      Re: Medical devices and US 220V electrics "Tom Del Rosso" <fizzbintuesday@that-google-mail-domain.com> - 2017-05-26 11:55 -0400
        Re: Medical devices and US 220V electrics krw@notreal.com - 2017-05-26 17:38 -0400
          Re: Medical devices and US 220V electrics "Tom Del Rosso" <fizzbintuesday@that-google-mail-domain.com> - 2017-05-26 20:32 -0400
            Re: Medical devices and US 220V electrics krw@notreal.com - 2017-05-26 22:20 -0400
              Re: Medical devices and US 220V electrics "Tom Del Rosso" <fizzbintuesday@that-google-mail-domain.com> - 2017-05-27 00:33 -0400
                Re: Medical devices and US 220V electrics krw@notreal.com - 2017-05-27 09:37 -0400
    Re: Medical devices and US 220V electrics legg <legg@nospam.magma.ca> - 2017-05-25 12:07 -0400
      Re: Medical devices and US 220V electrics krw@notreal.com - 2017-05-25 12:49 -0400
        Re: Medical devices and US 220V electrics Neon John <no@never.com> - 2017-05-28 15:56 -0400
          Re: Medical devices and US 220V electrics krw@notreal.com - 2017-05-28 16:59 -0400
        Re: Medical devices and US 220V electrics upsidedown@downunder.com - 2017-05-30 12:37 +0300
          Re: Medical devices and US 220V electrics krw@notreal.com - 2017-05-30 17:41 -0400
      Re: Medical devices and US 220V electrics gregz <zekor@comcast.net> - 2017-05-30 06:58 +0000
    Re: Medical devices and US 220V electrics rickman <gnuarm@gmail.com> - 2017-05-25 12:15 -0400
      Re: Medical devices and US 220V electrics Jon Elson <jmelson@wustl.edu> - 2017-05-25 15:07 -0500
        Re: Medical devices and US 220V electrics John Larkin <jjlarkin@highland_snip_technology.com> - 2017-05-25 13:14 -0700
          Re: Medical devices and US 220V electrics Jon Elson <jmelson@wustl.edu> - 2017-05-25 16:34 -0500
        Re: Medical devices and US 220V electrics krw@notreal.com - 2017-05-25 18:47 -0400
          Re: Medical devices and US 220V electrics Sjouke Burry <burrynulnulfour@ppllaanneett.nnll> - 2017-05-27 01:46 +0200
            Re: Medical devices and US 220V electrics krw@notreal.com - 2017-05-26 19:53 -0400
              Re: Medical devices and US 220V electrics Sjouke Burry <burrynulnulfour@ppllaanneett.nnll> - 2017-05-27 02:05 +0200
                Re: Medical devices and US 220V electrics krw@notreal.com - 2017-05-26 22:21 -0400
                  Re: Medical devices and US 220V electrics Sjouke Burry <burrynulnulfour@ppllaanneett.nnll> - 2017-05-27 04:25 +0200
                    Re: Medical devices and US 220V electrics krw@notreal.com - 2017-05-26 22:33 -0400
                      Re: Medical devices and US 220V electrics Sjouke Burry <burrynulnulfour@ppllaanneett.nnll> - 2017-05-27 21:48 +0200
    Re: Medical devices and US 220V electrics Don Y <blockedofcourse@foo.invalid> - 2017-05-25 11:20 -0700
    Re: Medical devices and US 220V electrics Jon Elson <jmelson@wustl.edu> - 2017-05-25 14:57 -0500
      Re: Medical devices and US 220V electrics RBlack <news@rblack01.plus.com> - 2017-05-26 12:17 +0100
        Re: Medical devices and US 220V electrics tabbypurr@gmail.com - 2017-05-26 04:53 -0700
        Re: Medical devices and US 220V electrics Phil Allison <pallison49@gmail.com> - 2017-05-26 06:00 -0700
        Re: Medical devices and US 220V electrics rickman <gnuarm@gmail.com> - 2017-05-26 12:05 -0400
        Re: Medical devices and US 220V electrics krw@notreal.com - 2017-05-26 17:51 -0400
          Re: Medical devices and US 220V electrics George Herold <gherold@teachspin.com> - 2017-05-26 17:54 -0700
            Re: Medical devices and US 220V electrics krw@notreal.com - 2017-05-26 22:24 -0400
        Re: Medical devices and US 220V electrics upsidedown@downunder.com - 2017-05-27 00:52 +0300
          Re: Medical devices and US 220V electrics Lasse Langwadt Christensen <langwadt@fonz.dk> - 2017-05-26 15:39 -0700
        Re: Medical devices and US 220V electrics Neon John <no@never.com> - 2017-05-28 16:34 -0400
          Re: Medical devices and US 220V electrics krw@notreal.com - 2017-05-28 17:26 -0400
            Re: Medical devices and US 220V electrics Neon John <no@never.com> - 2017-05-29 12:12 -0400
              Re: Medical devices and US 220V electrics krw@notreal.com - 2017-05-29 14:26 -0400
    Re: Medical devices and US 220V electrics Tim Wescott <tim@seemywebsite.really> - 2017-05-29 00:08 -0500
    Re: Medical devices and US 220V electrics David Lesher <wb8foz@panix.com> - 2017-05-29 20:24 +0000
      Re: Medical devices and US 220V electrics krw@notreal.com - 2017-05-29 16:37 -0400
        Re: Medical devices and US 220V electrics David Lesher <wb8foz@panix.com> - 2017-05-30 16:33 +0000
          Re: Medical devices and US 220V electrics Jim Thompson <To-Email-Use-The-Envelope-Icon@On-My-Web-Site.com> - 2017-05-30 09:46 -0700
          Re: Medical devices and US 220V electrics krw@notreal.com - 2017-05-30 17:45 -0400
            Re: Medical devices and US 220V electrics David Lesher <wb8foz@panix.com> - 2017-05-31 03:31 +0000
              Re: Medical devices and US 220V electrics krw@notreal.com - 2017-05-31 17:58 -0400
                Re: Medical devices and US 220V electrics Jan Panteltje <pNa0nStpealmtje@yahoo.com> - 2017-06-01 07:54 +0000
                  Re: Medical devices and US 220V electrics upsidedown@downunder.com - 2017-06-01 12:49 +0300
                    Re: Medical devices and US 220V electrics Neon John <no@never.com> - 2017-06-01 10:28 -0400
                      Re: Medical devices and US 220V electrics Jan Panteltje <pNa0nStpealmtje@yahoo.com> - 2017-06-01 14:45 +0000
                      Re: Medical devices and US 220V electrics Neon John <no@never.com> - 2017-06-01 18:47 -0400
                        Re: Medical devices and US 220V electrics Lasse Langwadt Christensen <langwadt@fonz.dk> - 2017-06-01 15:57 -0700
                          Re: Medical devices and US 220V electrics Jan Panteltje <pNa0nStpealmtje@yahoo.com> - 2017-06-02 07:21 +0000
                        Re: Medical devices and US 220V electrics krw@notreal.com - 2017-06-01 18:59 -0400
                Re: Medical devices and US 220V electrics David Lesher <wb8foz@panix.com> - 2017-06-03 14:00 +0000
                  Re: Medical devices and US 220V electrics krw@notreal.com - 2017-06-03 11:19 -0400
      Re: Medical devices and US 220V electrics upsidedown@downunder.com - 2017-05-30 01:16 +0300
        Re: Medical devices and US 220V electrics tabbypurr@gmail.com - 2017-05-29 22:31 -0700
          Re: Medical devices and US 220V electrics Phil Allison <pallison49@gmail.com> - 2017-05-29 23:06 -0700
            Re: Medical devices and US 220V electrics tabbypurr@gmail.com - 2017-05-29 23:25 -0700
              Re: Medical devices and US 220V electrics Phil Allison <pallison49@gmail.com> - 2017-05-29 23:39 -0700
                Re: Medical devices and US 220V electrics tabbypurr@gmail.com - 2017-05-30 00:19 -0700
              Re: Medical devices and US 220V electrics rickman <gnuarm@gmail.com> - 2017-05-30 10:40 -0400
      Re: Medical devices and US 220V electrics rickman <gnuarm@gmail.com> - 2017-05-30 10:37 -0400
    Re: Medical devices and US 220V electrics Jim Thompson <To-Email-Use-The-Envelope-Icon@On-My-Web-Site.com> - 2017-05-30 16:58 -0700
      Re: Medical devices and US 220V electrics Don Y <blockedofcourse@foo.invalid> - 2017-05-30 22:15 -0700
        Re: Medical devices and US 220V electrics Jim Thompson <To-Email-Use-The-Envelope-Icon@On-My-Web-Site.com> - 2017-05-31 07:38 -0700
      Re: Medical devices and US 220V electrics Don Kuenz <g@crcomp.net> - 2017-05-31 14:05 +0000
        Re: Medical devices and US 220V electrics Jim Thompson <To-Email-Use-The-Envelope-Icon@On-My-Web-Site.com> - 2017-05-31 07:40 -0700
        Re: Medical devices and US 220V electrics Don Y <blockedofcourse@foo.invalid> - 2017-05-31 09:37 -0700

Page 2 of 5 — ← Prev page 1 [2] 3 4 5  Next page →


#461954

From"Tom Del Rosso" <fizzbintuesday@that-google-mail-domain.com>
Date2017-05-27 00:33 -0400
Message-ID<ogavie$105a$1@gioia.aioe.org>
In reply to#461941
krw@notreal.com wrote:
> On Fri, 26 May 2017 20:32:30 -0400, "Tom Del Rosso"
> <fizzbintuesday@that-google-mail-domain.com> wrote:
>
>> krw@notreal.com wrote:
>>> On Fri, 26 May 2017 11:55:33 -0400, "Tom Del Rosso"
>>> <fizzbintuesday@that-google-mail-domain.com> wrote:
>>>
>>>> upsidedown@downunder.com wrote:
>>>>> On Thu, 25 May 2017 13:05:28 +0100, RBlack
>>>>> <news@rblack01.plus.com> wrote:
>>>>>
>>>>>> We are working on a medical product, which will draw about 3 kW
>>>>>> from the mains.  This is new territory for us, all our previous
>>>>>> products were a few hundred watts max so an off-the-shelf
>>>>>> auto-ranging PSU with a suitable IEC lead was OK for any country
>>>>>> in the world.
>>>>>
>>>>> Is this peak or average ?
>>>>> Is it 3 kW or 3 kVA ? What power factor ?
>>>>>
>>>>>> 3 kW is OK for a standard outlet in 220V countries, but for North
>>>>>> America, Japan etc we are over the limit for a standard 110V
>>>>>> outlet.
>>>>>
>>>>> It is not OK for 220-240 V outlets with 10 A fuses. You would have
>>>>> to install a dedicated 16 A outlet.
>>>>>
>>>>> Any additional loads on the same fuse might eventually blow the
>>>>> fuse, a situation which is not appreciated in a hospital
>>>>> environment.
>>>>
>>>> When installing a new oven in an old kitchen it's not unusual to
>>>> install a new circuit.  Surely hospitals buying very big expensive
>>>> equipment can have a new circuit installed.
>>>
>>> Huh?  In a *very* old kitchen, maybe. In a house that old, likely
>>> the entire house needs to be rewired.
>>
>> No.  If the house is only a few decades old it probably wouldn't have
>> enough in the kitchen for a fridge and a self-cleaning gas oven.
>>
> Fridges run on 120V.  Self-cleaning *GAS* ovens don't take much
> electricity at all (electric ones don't either).  If you're switching
> from gas to electricity, sure, but what nut does that?

The self-cleaning gas ovens I've seen use electric elements for cleaning 
and modern codes around here require a separate circuit for it.  A 
microwave adds another 10 amps, so kitchen renovations often require 
adding a couple of circuits.  Just changing the oven could require one 
new circuit and the OP's product is probably a lot more expensive than a 
range.


[toc] | [prev] | [next] | [standalone]


#461983

Fromkrw@notreal.com
Date2017-05-27 09:37 -0400
Message-ID<940jicl5ten9rleniu9h06pomafs8l4j30@4ax.com>
In reply to#461954
On Sat, 27 May 2017 00:33:18 -0400, "Tom Del Rosso"
<fizzbintuesday@that-google-mail-domain.com> wrote:

>krw@notreal.com wrote:
>> On Fri, 26 May 2017 20:32:30 -0400, "Tom Del Rosso"
>> <fizzbintuesday@that-google-mail-domain.com> wrote:
>>
>>> krw@notreal.com wrote:
>>>> On Fri, 26 May 2017 11:55:33 -0400, "Tom Del Rosso"
>>>> <fizzbintuesday@that-google-mail-domain.com> wrote:
>>>>
>>>>> upsidedown@downunder.com wrote:
>>>>>> On Thu, 25 May 2017 13:05:28 +0100, RBlack
>>>>>> <news@rblack01.plus.com> wrote:
>>>>>>
>>>>>>> We are working on a medical product, which will draw about 3 kW
>>>>>>> from the mains.  This is new territory for us, all our previous
>>>>>>> products were a few hundred watts max so an off-the-shelf
>>>>>>> auto-ranging PSU with a suitable IEC lead was OK for any country
>>>>>>> in the world.
>>>>>>
>>>>>> Is this peak or average ?
>>>>>> Is it 3 kW or 3 kVA ? What power factor ?
>>>>>>
>>>>>>> 3 kW is OK for a standard outlet in 220V countries, but for North
>>>>>>> America, Japan etc we are over the limit for a standard 110V
>>>>>>> outlet.
>>>>>>
>>>>>> It is not OK for 220-240 V outlets with 10 A fuses. You would have
>>>>>> to install a dedicated 16 A outlet.
>>>>>>
>>>>>> Any additional loads on the same fuse might eventually blow the
>>>>>> fuse, a situation which is not appreciated in a hospital
>>>>>> environment.
>>>>>
>>>>> When installing a new oven in an old kitchen it's not unusual to
>>>>> install a new circuit.  Surely hospitals buying very big expensive
>>>>> equipment can have a new circuit installed.
>>>>
>>>> Huh?  In a *very* old kitchen, maybe. In a house that old, likely
>>>> the entire house needs to be rewired.
>>>
>>> No.  If the house is only a few decades old it probably wouldn't have
>>> enough in the kitchen for a fridge and a self-cleaning gas oven.
>>>
>> Fridges run on 120V.  Self-cleaning *GAS* ovens don't take much
>> electricity at all (electric ones don't either).  If you're switching
>> from gas to electricity, sure, but what nut does that?
>
>The self-cleaning gas ovens I've seen use electric elements for cleaning 
>and modern codes around here require a separate circuit for it.  A 
>microwave adds another 10 amps, so kitchen renovations often require 
>adding a couple of circuits.  Just changing the oven could require one 
>new circuit and the OP's product is probably a lot more expensive than a 
>range.

The point is that adding new circuits to existing homes is usually a
*big* deal (tearing up many walls to run wiring) and is rarely done,
unless the entire kitchen is being remodeled.  Then, all circuits must
be brought up to current code.

Replacing an electric range with another electric range is no big
deal.  New ones, even self-cleaning, don't take any more power than
those from fifty years ago.

[toc] | [prev] | [next] | [standalone]


#461674

Fromlegg <legg@nospam.magma.ca>
Date2017-05-25 12:07 -0400
Message-ID<m7vdichtn4d8039urkung7btpvo0377u3j@4ax.com>
In reply to#461639
On Thu, 25 May 2017 13:05:28 +0100, RBlack <news@rblack01.plus.com>
wrote:

>Hi,
>
>We are working on a medical product, which will draw about 3 kW from the 
>mains.  This is new territory for us, all our previous products were a 
>few hundred watts max so an off-the-shelf auto-ranging PSU with a 
>suitable IEC lead was OK for any country in the world.
>
>3 kW is OK for a standard outlet in 220V countries, but for North 
>America, Japan etc we are over the limit for a standard 110V outlet.
>
>I only know as much about US electrical installations as I've read, a 
>bit of Googling suggests the product will need a NEMA 6-15 220V outlet.  
>But how common are these in hospitals?  Anybody have any experience of 
>this stuff?
>
>It has been suggested (not by me I hasten to add) that we split the 
>loads within the product up and give it two 110V inlets, to get around 
>the customer having to install a 'special' outlet for it.  This sounds 
>like a Really Bad Idea and a regulatory nightmare to me, so if 220V 
>outlets are commonly available anyway I can shoot it down before it gets 
>too far.
>
>TIA

Split phase 208VAC is not uncommon in NA - used to be standard for
Kitchen stove, laundry drier or workbench hookups.
Up to 20A/phase using 4wire armoured or flex cabling to iether
duplexed 2x15 or 2x20A 120V wall outlets or single 15/20A outlets.
They need separate but coupled breakers on each line.

If the power level you are talking about is already typically used in
the application, then you should use the power couplers presently
employed in the medical 'industry' for that application.

Equipment with that type of power consumption are not normally
considered to be either portable or transportable, so a power
requirement isn't a big issue. It is not likely to be included in any
situation that has patient-applied parts, either, so the 'medical'
part of it's labeling is likely only there to avoid commercial
restrictions on similar products, like EMC........ 

[toc] | [prev] | [next] | [standalone]


#461682

Fromkrw@notreal.com
Date2017-05-25 12:49 -0400
Message-ID<ca2eicti29v41v6dl8td40e2cn5125bkgq@4ax.com>
In reply to#461674
On Thu, 25 May 2017 12:07:59 -0400, legg <legg@nospam.magma.ca> wrote:

>On Thu, 25 May 2017 13:05:28 +0100, RBlack <news@rblack01.plus.com>
>wrote:
>
>>Hi,
>>
>>We are working on a medical product, which will draw about 3 kW from the 
>>mains.  This is new territory for us, all our previous products were a 
>>few hundred watts max so an off-the-shelf auto-ranging PSU with a 
>>suitable IEC lead was OK for any country in the world.
>>
>>3 kW is OK for a standard outlet in 220V countries, but for North 
>>America, Japan etc we are over the limit for a standard 110V outlet.
>>
>>I only know as much about US electrical installations as I've read, a 
>>bit of Googling suggests the product will need a NEMA 6-15 220V outlet.  
>>But how common are these in hospitals?  Anybody have any experience of 
>>this stuff?
>>
>>It has been suggested (not by me I hasten to add) that we split the 
>>loads within the product up and give it two 110V inlets, to get around 
>>the customer having to install a 'special' outlet for it.  This sounds 
>>like a Really Bad Idea and a regulatory nightmare to me, so if 220V 
>>outlets are commonly available anyway I can shoot it down before it gets 
>>too far.
>>
>>TIA
>
>Split phase 208VAC is not uncommon in NA - used to be standard for
>Kitchen stove, laundry drier or workbench hookups.
>Up to 20A/phase using 4wire armoured or flex cabling to iether
>duplexed 2x15 or 2x20A 120V wall outlets or single 15/20A outlets.
>They need separate but coupled breakers on each line.

You're describing split-phase 240V; two 120V circuits split from a
240V circuit (by the center tap of a transformer).  208V is the
voltage across two phases of a three phase 120V circuit, often used in
commercial lighting but not used in residential settings at all.

>If the power level you are talking about is already typically used in
>the application, then you should use the power couplers presently
>employed in the medical 'industry' for that application.
>
>Equipment with that type of power consumption are not normally
>considered to be either portable or transportable, so a power
>requirement isn't a big issue. It is not likely to be included in any
>situation that has patient-applied parts, either, so the 'medical'
>part of it's labeling is likely only there to avoid commercial
>restrictions on similar products, like EMC........ 

[toc] | [prev] | [next] | [standalone]


#462107

FromNeon John <no@never.com>
Date2017-05-28 15:56 -0400
Message-ID<miamichid098rv9v60stf9q0mskhb60tlf@4ax.com>
In reply to#461682
On Thu, 25 May 2017 12:49:40 -0400, krw@notreal.com wrote:


>>Split phase 208VAC is not uncommon in NA - used to be standard for
>>Kitchen stove, laundry drier or workbench hookups.
>>Up to 20A/phase using 4wire armoured or flex cabling to iether
>>duplexed 2x15 or 2x20A 120V wall outlets or single 15/20A outlets.
>>They need separate but coupled breakers on each line.

120/208 is common only in large apartment building in places like NYC.
IT is the bane of the residents who frequently have to resort to
208/240 boost autotransformers to get appliances like ACs and stoves
to work properly.

>
>You're describing split-phase 240V; two 120V circuits split from a
>240V circuit (by the center tap of a transformer).  208V is the
>voltage across two phases of a three phase 120V circuit, often used in
>commercial lighting but not used in residential settings at all.

Sure it is.  His device should be able to function from about 200
volts to 250 volts.

>>Equipment with that type of power consumption are not normally
>>considered to be either portable or transportable, so a power
>>requirement isn't a big issue. 

Ever seen a portable X-ray machine?

John
John DeArmond
http://www.neon-john.com
http://www.tnduction.com 
Tellico Plains, Occupied TN
See website for email address

[toc] | [prev] | [next] | [standalone]


#462118

Fromkrw@notreal.com
Date2017-05-28 16:59 -0400
Message-ID<peemic1ejn14q68c3r47m57cdj1ikgfsr5@4ax.com>
In reply to#462107
On Sun, 28 May 2017 15:56:47 -0400, Neon John <no@never.com> wrote:

>On Thu, 25 May 2017 12:49:40 -0400, krw@notreal.com wrote:
>
>
>>>Split phase 208VAC is not uncommon in NA - used to be standard for
>>>Kitchen stove, laundry drier or workbench hookups.
>>>Up to 20A/phase using 4wire armoured or flex cabling to iether
>>>duplexed 2x15 or 2x20A 120V wall outlets or single 15/20A outlets.
>>>They need separate but coupled breakers on each line.
>
>120/208 is common only in large apartment building in places like NYC.
>IT is the bane of the residents who frequently have to resort to
>208/240 boost autotransformers to get appliances like ACs and stoves
>to work properly.
>
>>
>>You're describing split-phase 240V; two 120V circuits split from a
>>240V circuit (by the center tap of a transformer).  208V is the
>>voltage across two phases of a three phase 120V circuit, often used in
>>commercial lighting but not used in residential settings at all.
>
>Sure it is.  His device should be able to function from about 200
>volts to 250 volts.

No it is certainly *not*.  Don't be an ass.  

>>>Equipment with that type of power consumption are not normally
>>>considered to be either portable or transportable, so a power
>>>requirement isn't a big issue. 
>
>Ever seen a portable X-ray machine?

As I said...

[toc] | [prev] | [next] | [standalone]


#462276

Fromupsidedown@downunder.com
Date2017-05-30 12:37 +0300
Message-ID<a9eqiclvahn8aqlpjm4ts7hfmqufmkqqes@4ax.com>
In reply to#461682
On Thu, 25 May 2017 12:49:40 -0400, krw@notreal.com wrote:

>On Thu, 25 May 2017 12:07:59 -0400, legg <legg@nospam.magma.ca> wrote:
>
>>On Thu, 25 May 2017 13:05:28 +0100, RBlack <news@rblack01.plus.com>
>>wrote:
>>
>>>Hi,
>>>
>>>We are working on a medical product, which will draw about 3 kW from the 
>>>mains.  This is new territory for us, all our previous products were a 
>>>few hundred watts max so an off-the-shelf auto-ranging PSU with a 
>>>suitable IEC lead was OK for any country in the world.
>>>
>>>3 kW is OK for a standard outlet in 220V countries, but for North 
>>>America, Japan etc we are over the limit for a standard 110V outlet.
>>>
>>>I only know as much about US electrical installations as I've read, a 
>>>bit of Googling suggests the product will need a NEMA 6-15 220V outlet.  
>>>But how common are these in hospitals?  Anybody have any experience of 
>>>this stuff?
>>>
>>>It has been suggested (not by me I hasten to add) that we split the 
>>>loads within the product up and give it two 110V inlets, to get around 
>>>the customer having to install a 'special' outlet for it.  This sounds 
>>>like a Really Bad Idea and a regulatory nightmare to me, so if 220V 
>>>outlets are commonly available anyway I can shoot it down before it gets 
>>>too far.
>>>
>>>TIA
>>
>>Split phase 208VAC is not uncommon in NA - used to be standard for
>>Kitchen stove, laundry drier or workbench hookups.
>>Up to 20A/phase using 4wire armoured or flex cabling to iether
>>duplexed 2x15 or 2x20A 120V wall outlets or single 15/20A outlets.
>>They need separate but coupled breakers on each line.
>
>You're describing split-phase 240V; two 120V circuits split from a
>240V circuit (by the center tap of a transformer).  208V is the
>voltage across two phases of a three phase 120V circuit, often used in
>commercial lighting but not used in residential settings at all.

If you have 208 V, there must be a full 120/208 V three phase feed
nearby. 

To the OP, when 3 phase is available, why not use a full 3 phase (6
pulse) rectifier. It just requires two extra diodes compared to a full
wave single phase rectifier. When split phase 240 V is available, only
4 rectifiers work, but with three phase 120/208 V all 6 rectifiers are
working. The rectified DC voltage is similar.

In Europe with 230 V 16 A would give similar DC voltages. 

A 3x16 A 230/400 V feed would give considerably higher DC voltages.

Thus, the device power supply should be built as an ordinary three
phase 6 pulse rectifier with a storage capacitor (for single phase). A
3-phase mains connector on the device and all you need to wire the
mains cable for 120/208 V, 2x120 V, 230 V (or possibly 230/400 V) with
no switching needed in the device.

[toc] | [prev] | [next] | [standalone]


#462339

Fromkrw@notreal.com
Date2017-05-30 17:41 -0400
Message-ID<fkpricdtvsqr55ame6227gfpra970rbsfj@4ax.com>
In reply to#462276
On Tue, 30 May 2017 12:37:41 +0300, upsidedown@downunder.com wrote:

>On Thu, 25 May 2017 12:49:40 -0400, krw@notreal.com wrote:
>
>>On Thu, 25 May 2017 12:07:59 -0400, legg <legg@nospam.magma.ca> wrote:
>>
>>>On Thu, 25 May 2017 13:05:28 +0100, RBlack <news@rblack01.plus.com>
>>>wrote:
>>>
>>>>Hi,
>>>>
>>>>We are working on a medical product, which will draw about 3 kW from the 
>>>>mains.  This is new territory for us, all our previous products were a 
>>>>few hundred watts max so an off-the-shelf auto-ranging PSU with a 
>>>>suitable IEC lead was OK for any country in the world.
>>>>
>>>>3 kW is OK for a standard outlet in 220V countries, but for North 
>>>>America, Japan etc we are over the limit for a standard 110V outlet.
>>>>
>>>>I only know as much about US electrical installations as I've read, a 
>>>>bit of Googling suggests the product will need a NEMA 6-15 220V outlet.  
>>>>But how common are these in hospitals?  Anybody have any experience of 
>>>>this stuff?
>>>>
>>>>It has been suggested (not by me I hasten to add) that we split the 
>>>>loads within the product up and give it two 110V inlets, to get around 
>>>>the customer having to install a 'special' outlet for it.  This sounds 
>>>>like a Really Bad Idea and a regulatory nightmare to me, so if 220V 
>>>>outlets are commonly available anyway I can shoot it down before it gets 
>>>>too far.
>>>>
>>>>TIA
>>>
>>>Split phase 208VAC is not uncommon in NA - used to be standard for
>>>Kitchen stove, laundry drier or workbench hookups.
>>>Up to 20A/phase using 4wire armoured or flex cabling to iether
>>>duplexed 2x15 or 2x20A 120V wall outlets or single 15/20A outlets.
>>>They need separate but coupled breakers on each line.
>>
>>You're describing split-phase 240V; two 120V circuits split from a
>>240V circuit (by the center tap of a transformer).  208V is the
>>voltage across two phases of a three phase 120V circuit, often used in
>>commercial lighting but not used in residential settings at all.
>
>If you have 208 V, there must be a full 120/208 V three phase feed
>nearby. 

If you have 240V (or 120V) you also have three phase feed nearby.
There is nothing that says you have all three (of the phases), in any
of the above cases.

[toc] | [prev] | [next] | [standalone]


#462264

Fromgregz <zekor@comcast.net>
Date2017-05-30 06:58 +0000
Message-ID<261373338517820847.943037zekor-comcast.net@news.eternal-september.org>
In reply to#461674
legg <legg@nospam.magma.ca> wrote:
> On Thu, 25 May 2017 13:05:28 +0100, RBlack <news@rblack01.plus.com>
> wrote:
> 
>> Hi,
>> 
>> We are working on a medical product, which will draw about 3 kW from the 
>> mains.  This is new territory for us, all our previous products were a 
>> few hundred watts max so an off-the-shelf auto-ranging PSU with a 
>> suitable IEC lead was OK for any country in the world.
>> 
>> 3 kW is OK for a standard outlet in 220V countries, but for North 
>> America, Japan etc we are over the limit for a standard 110V outlet.
>> 
>> I only know as much about US electrical installations as I've read, a 
>> bit of Googling suggests the product will need a NEMA 6-15 220V outlet.  
>> But how common are these in hospitals?  Anybody have any experience of 
>> this stuff?
>> 
>> It has been suggested (not by me I hasten to add) that we split the 
>> loads within the product up and give it two 110V inlets, to get around 
>> the customer having to install a 'special' outlet for it.  This sounds 
>> like a Really Bad Idea and a regulatory nightmare to me, so if 220V 
>> outlets are commonly available anyway I can shoot it down before it gets 
>> too far.
>> 
>> TIA
> 
> Split phase 208VAC is not uncommon in NA - used to be standard for
> Kitchen stove, laundry drier or workbench hookups.
> Up to 20A/phase using 4wire armoured or flex cabling to iether
> duplexed 2x15 or 2x20A 120V wall outlets or single 15/20A outlets.
> They need separate but coupled breakers on each line.
> 
> If the power level you are talking about is already typically used in
> the application, then you should use the power couplers presently
> employed in the medical 'industry' for that application.
> 
> Equipment with that type of power consumption are not normally
> considered to be either portable or transportable, so a power
> requirement isn't a big issue. It is not likely to be included in any
> situation that has patient-applied parts, either, so the 'medical'
> part of it's labeling is likely only there to avoid commercial
> restrictions on similar products, like EMC........

208 might be more common in hospitals. 240 in homes.

Greg

[toc] | [prev] | [next] | [standalone]


#461675

Fromrickman <gnuarm@gmail.com>
Date2017-05-25 12:15 -0400
Message-ID<og6vpb$nad$1@dont-email.me>
In reply to#461639
RBlack wrote on 5/25/2017 8:05 AM:
> Hi,
>
> We are working on a medical product, which will draw about 3 kW from the
> mains.  This is new territory for us, all our previous products were a
> few hundred watts max so an off-the-shelf auto-ranging PSU with a
> suitable IEC lead was OK for any country in the world.
>
> 3 kW is OK for a standard outlet in 220V countries, but for North
> America, Japan etc we are over the limit for a standard 110V outlet.
>
> I only know as much about US electrical installations as I've read, a
> bit of Googling suggests the product will need a NEMA 6-15 220V outlet.
> But how common are these in hospitals?  Anybody have any experience of
> this stuff?
>
> It has been suggested (not by me I hasten to add) that we split the
> loads within the product up and give it two 110V inlets, to get around
> the customer having to install a 'special' outlet for it.  This sounds
> like a Really Bad Idea and a regulatory nightmare to me, so if 220V
> outlets are commonly available anyway I can shoot it down before it gets
> too far.

No, 220 VAC is not common in the US, at least not in homes or offices. 
I don't know what hospitals might have.  If you are talking about 
installing this in a lab setting, then providing 220 VAC is not really 
an issue, but it likely will require adding an outlet rather than just 
plugging it in.

All buildings have 220 VAC at the fuse panel, it is only distributed to 
the equipment that needs it like furnaces, clothes dryers and stoves. 
Office settings are often wired with both phases for the 110 VAC outlets 
with every other one on alternate phases.  This helps to balance the 
load on the two phases.  So there may well be 220 volts in a given 
outlet box, you just have to install a different outlet.  In homes they 
only run three wires to each outlet box, AC, common and earth.  So any 
220 VAC outlets will require a new run unless your unit goes in next to 
a dryer or stove that can be off when your unit runs.  I don't know 
code, but that is likely not allowed since running both could overload 
the circuit.

The bottom line is 220 VAC outlets are not commonly available, but 220 
VAC is available in all buildings if you want to run a line for a new 
outlet.

-- 

Rick C

[toc] | [prev] | [next] | [standalone]


#461718

FromJon Elson <jmelson@wustl.edu>
Date2017-05-25 15:07 -0500
Message-ID<vJKdnRqqH4lTpbrEnZ2dnUU7-cXNnZ2d@giganews.com>
In reply to#461675
rickman wrote:

> No, 220 VAC is not common in the US, at least not in homes or offices.
> I don't know what hospitals might have.

Actually, 120/208 Wye service is quite common in larger offices.  Might not 
have it in the typical storefront-type building, but almost any multi-level 
office building will likely have that system.  It gives lots of 120 V 
single-phase outlets, and 208 V between any two hots.  Smaller air 
conditioners would have 3-phase compressors off the 208 mains.  The building 
I work in has 120/208 Wye in the offices, 120/208 Wye PLUS 230 Delta in the 
lab space and 480 in the mechanical areas.  

3 Phase is VERY rare in single-family homes, but common in apartment 
buildings.  And, certainly, any hospital will have 3-phase panels throughout 
the building.

Jon

[toc] | [prev] | [next] | [standalone]


#461720

FromJohn Larkin <jjlarkin@highland_snip_technology.com>
Date2017-05-25 13:14 -0700
Message-ID<4geeicda411uf4rh5vu8b2hb8k65uk7ufa@4ax.com>
In reply to#461718
On Thu, 25 May 2017 15:07:13 -0500, Jon Elson <jmelson@wustl.edu>
wrote:

>rickman wrote:
>
>> No, 220 VAC is not common in the US, at least not in homes or offices.
>> I don't know what hospitals might have.
>
>Actually, 120/208 Wye service is quite common in larger offices. 

We have 120/240 3-phase, which is called a "stinger" service. That's
3-phase 240 line-to-line, with neutral being the center tap of one
side of the triangle.

https://en.wikipedia.org/wiki/High-leg_delta

I suspect that any hospital could furnish 220 or 240 if equipment
needs it.


-- 

John Larkin         Highland Technology, Inc
picosecond timing   precision measurement 

jlarkin att highlandtechnology dott com
http://www.highlandtechnology.com

[toc] | [prev] | [next] | [standalone]


#461726

FromJon Elson <jmelson@wustl.edu>
Date2017-05-25 16:34 -0500
Message-ID<SM-dnXiPysrZ0LrEnZ2dnUU7-KfNnZ2d@giganews.com>
In reply to#461720
John Larkin wrote:

> On Thu, 25 May 2017 15:07:13 -0500, Jon Elson <jmelson@wustl.edu>
> wrote:
> 
>>rickman wrote:
>>
>>> No, 220 VAC is not common in the US, at least not in homes or offices.
>>> I don't know what hospitals might have.
>>
>>Actually, 120/208 Wye service is quite common in larger offices.
> 
> We have 120/240 3-phase, which is called a "stinger" service. That's
> 3-phase 240 line-to-line, with neutral being the center tap of one
> side of the triangle.
> 
Yes, there are legacy corner-grounded Delta and center-grounded Delta 
systems.  These are not balanced around the center of the 3-phase system.
Corner-grounded Delta systems generally use 2-pole breakers, as the 3rd leg 
of the 3-phases is at ground.  What Rick refers to above is a center-
grounded Delta, which allows you to have both 120 and 240 just like in 
residential service in the US, but also 3-phase 240 V power, all in one 
breaker panel, if you like.  Commonly used in shops year ago, so you could 
supply all typical loads from one service.

I'm pretty sure you can't get either of these types of service installed 
today.

Jon

[toc] | [prev] | [next] | [standalone]


#461738

Fromkrw@notreal.com
Date2017-05-25 18:47 -0400
Message-ID<mkneic5tm98fgqulm9lg6euvg98q8g3987@4ax.com>
In reply to#461718
On Thu, 25 May 2017 15:07:13 -0500, Jon Elson <jmelson@wustl.edu>
wrote:

>rickman wrote:
>
>> No, 220 VAC is not common in the US, at least not in homes or offices.
>> I don't know what hospitals might have.
>
>Actually, 120/208 Wye service is quite common in larger offices.  Might not 
>have it in the typical storefront-type building, but almost any multi-level 
>office building will likely have that system.  It gives lots of 120 V 
>single-phase outlets, and 208 V between any two hots.  Smaller air 
>conditioners would have 3-phase compressors off the 208 mains.  The building 
>I work in has 120/208 Wye in the offices, 120/208 Wye PLUS 230 Delta in the 
>lab space and 480 in the mechanical areas.  
>
>3 Phase is VERY rare in single-family homes, but common in apartment 
>buildings.  And, certainly, any hospital will have 3-phase panels throughout 
>the building.

3-Phase will certainly be common in large apartment buildings but
it'll never be found inside a single apartment.  Think of the building
as a neighborhood.  ;-)

[toc] | [prev] | [next] | [standalone]


#461913

FromSjouke Burry <burrynulnulfour@ppllaanneett.nnll>
Date2017-05-27 01:46 +0200
Message-ID<5928bed3$0$1714$e4fe514c@textnews.kpn.nl>
In reply to#461738
On 26.05.17 0:47, krw@notreal.com wrote:
> On Thu, 25 May 2017 15:07:13 -0500, Jon Elson <jmelson@wustl.edu>
> wrote:
>
>> rickman wrote:
>>
>>> No, 220 VAC is not common in the US, at least not in homes or offices.
>>> I don't know what hospitals might have.
>>
>> Actually, 120/208 Wye service is quite common in larger offices.  Might not
>> have it in the typical storefront-type building, but almost any multi-level
>> office building will likely have that system.  It gives lots of 120 V
>> single-phase outlets, and 208 V between any two hots.  Smaller air
>> conditioners would have 3-phase compressors off the 208 mains.  The building
>> I work in has 120/208 Wye in the offices, 120/208 Wye PLUS 230 Delta in the
>> lab space and 480 in the mechanical areas.
>>
>> 3 Phase is VERY rare in single-family homes, but common in apartment
>> buildings.  And, certainly, any hospital will have 3-phase panels throughout
>> the building.
>
> 3-Phase will certainly be common in large apartment buildings but
> it'll never be found inside a single apartment.  Think of the building
> as a neighborhood.  ;-)
>
Hmm... I have a 220/380 3 phase cable feeding into my house, although I
use only one of them.(In the dim past each house got current from
1 of those 3 wires)

[toc] | [prev] | [next] | [standalone]


#461914

Fromkrw@notreal.com
Date2017-05-26 19:53 -0400
Message-ID<0ufhicllg893ue3gqsgf13q31p92ark592@4ax.com>
In reply to#461913
On Sat, 27 May 2017 01:46:41 +0200, Sjouke Burry
<burrynulnulfour@ppllaanneett.nnll> wrote:

>On 26.05.17 0:47, krw@notreal.com wrote:
>> On Thu, 25 May 2017 15:07:13 -0500, Jon Elson <jmelson@wustl.edu>
>> wrote:
>>
>>> rickman wrote:
>>>
>>>> No, 220 VAC is not common in the US, at least not in homes or offices.
>>>> I don't know what hospitals might have.
>>>
>>> Actually, 120/208 Wye service is quite common in larger offices.  Might not
>>> have it in the typical storefront-type building, but almost any multi-level
>>> office building will likely have that system.  It gives lots of 120 V
>>> single-phase outlets, and 208 V between any two hots.  Smaller air
>>> conditioners would have 3-phase compressors off the 208 mains.  The building
>>> I work in has 120/208 Wye in the offices, 120/208 Wye PLUS 230 Delta in the
>>> lab space and 480 in the mechanical areas.
>>>
>>> 3 Phase is VERY rare in single-family homes, but common in apartment
>>> buildings.  And, certainly, any hospital will have 3-phase panels throughout
>>> the building.
>>
>> 3-Phase will certainly be common in large apartment buildings but
>> it'll never be found inside a single apartment.  Think of the building
>> as a neighborhood.  ;-)
>>
>Hmm... I have a 220/380 3 phase cable feeding into my house, although I
>use only one of them.(In the dim past each house got current from
>1 of those 3 wires)

My house?  Each house?  Please explain.

[toc] | [prev] | [next] | [standalone]


#461916

FromSjouke Burry <burrynulnulfour@ppllaanneett.nnll>
Date2017-05-27 02:05 +0200
Message-ID<5928c337$0$1802$e4fe514c@textnews.kpn.nl>
In reply to#461914
On 27.05.17 1:53, krw@notreal.com wrote:
> On Sat, 27 May 2017 01:46:41 +0200, Sjouke Burry
> <burrynulnulfour@ppllaanneett.nnll> wrote:
>
>> On 26.05.17 0:47, krw@notreal.com wrote:
>>> On Thu, 25 May 2017 15:07:13 -0500, Jon Elson <jmelson@wustl.edu>
>>> wrote:
>>>
>>>> rickman wrote:
>>>>
>>>>> No, 220 VAC is not common in the US, at least not in homes or offices.
>>>>> I don't know what hospitals might have.
>>>>
>>>> Actually, 120/208 Wye service is quite common in larger offices.  Might not
>>>> have it in the typical storefront-type building, but almost any multi-level
>>>> office building will likely have that system.  It gives lots of 120 V
>>>> single-phase outlets, and 208 V between any two hots.  Smaller air
>>>> conditioners would have 3-phase compressors off the 208 mains.  The building
>>>> I work in has 120/208 Wye in the offices, 120/208 Wye PLUS 230 Delta in the
>>>> lab space and 480 in the mechanical areas.
>>>>
>>>> 3 Phase is VERY rare in single-family homes, but common in apartment
>>>> buildings.  And, certainly, any hospital will have 3-phase panels throughout
>>>> the building.
>>>
>>> 3-Phase will certainly be common in large apartment buildings but
>>> it'll never be found inside a single apartment.  Think of the building
>>> as a neighborhood.  ;-)
>>>
>> Hmm... I have a 220/380 3 phase cable feeding into my house, although I
>> use only one of them.(In the dim past each house got current from
>> 1 of those 3 wires)
>
> My house?  Each house?  Please explain.
>
3 houses, mine is the middle one, and each phase feeding 1 house.
That way, I end up with  a 3phase power cable.

[toc] | [prev] | [next] | [standalone]


#461942

Fromkrw@notreal.com
Date2017-05-26 22:21 -0400
Message-ID<kkohict1m08d0orl48p52vh2akpj6l7nks@4ax.com>
In reply to#461916
On Sat, 27 May 2017 02:05:24 +0200, Sjouke Burry
<burrynulnulfour@ppllaanneett.nnll> wrote:

>On 27.05.17 1:53, krw@notreal.com wrote:
>> On Sat, 27 May 2017 01:46:41 +0200, Sjouke Burry
>> <burrynulnulfour@ppllaanneett.nnll> wrote:
>>
>>> On 26.05.17 0:47, krw@notreal.com wrote:
>>>> On Thu, 25 May 2017 15:07:13 -0500, Jon Elson <jmelson@wustl.edu>
>>>> wrote:
>>>>
>>>>> rickman wrote:
>>>>>
>>>>>> No, 220 VAC is not common in the US, at least not in homes or offices.
>>>>>> I don't know what hospitals might have.
>>>>>
>>>>> Actually, 120/208 Wye service is quite common in larger offices.  Might not
>>>>> have it in the typical storefront-type building, but almost any multi-level
>>>>> office building will likely have that system.  It gives lots of 120 V
>>>>> single-phase outlets, and 208 V between any two hots.  Smaller air
>>>>> conditioners would have 3-phase compressors off the 208 mains.  The building
>>>>> I work in has 120/208 Wye in the offices, 120/208 Wye PLUS 230 Delta in the
>>>>> lab space and 480 in the mechanical areas.
>>>>>
>>>>> 3 Phase is VERY rare in single-family homes, but common in apartment
>>>>> buildings.  And, certainly, any hospital will have 3-phase panels throughout
>>>>> the building.
>>>>
>>>> 3-Phase will certainly be common in large apartment buildings but
>>>> it'll never be found inside a single apartment.  Think of the building
>>>> as a neighborhood.  ;-)
>>>>
>>> Hmm... I have a 220/380 3 phase cable feeding into my house, although I
>>> use only one of them.(In the dim past each house got current from
>>> 1 of those 3 wires)
>>
>> My house?  Each house?  Please explain.
>>
>3 houses, mine is the middle one, and each phase feeding 1 house.
>That way, I end up with  a 3phase power cable.

Why does the cable for the other two houses enter yours?  Row houses?

[toc] | [prev] | [next] | [standalone]


#461944

FromSjouke Burry <burrynulnulfour@ppllaanneett.nnll>
Date2017-05-27 04:25 +0200
Message-ID<5928e3ff$0$1680$e4fe514c@textnews.kpn.nl>
In reply to#461942
On 27.05.17 4:21, krw@notreal.com wrote:
> On Sat, 27 May 2017 02:05:24 +0200, Sjouke Burry
> <burrynulnulfour@ppllaanneett.nnll> wrote:
>
>> On 27.05.17 1:53, krw@notreal.com wrote:
>>> On Sat, 27 May 2017 01:46:41 +0200, Sjouke Burry
>>> <burrynulnulfour@ppllaanneett.nnll> wrote:
>>>
>>>> On 26.05.17 0:47, krw@notreal.com wrote:
>>>>> On Thu, 25 May 2017 15:07:13 -0500, Jon Elson <jmelson@wustl.edu>
>>>>> wrote:
>>>>>
>>>>>> rickman wrote:
>>>>>>
>>>>>>> No, 220 VAC is not common in the US, at least not in homes or offices.
>>>>>>> I don't know what hospitals might have.
>>>>>>
>>>>>> Actually, 120/208 Wye service is quite common in larger offices.  Might not
>>>>>> have it in the typical storefront-type building, but almost any multi-level
>>>>>> office building will likely have that system.  It gives lots of 120 V
>>>>>> single-phase outlets, and 208 V between any two hots.  Smaller air
>>>>>> conditioners would have 3-phase compressors off the 208 mains.  The building
>>>>>> I work in has 120/208 Wye in the offices, 120/208 Wye PLUS 230 Delta in the
>>>>>> lab space and 480 in the mechanical areas.
>>>>>>
>>>>>> 3 Phase is VERY rare in single-family homes, but common in apartment
>>>>>> buildings.  And, certainly, any hospital will have 3-phase panels throughout
>>>>>> the building.
>>>>>
>>>>> 3-Phase will certainly be common in large apartment buildings but
>>>>> it'll never be found inside a single apartment.  Think of the building
>>>>> as a neighborhood.  ;-)
>>>>>
>>>> Hmm... I have a 220/380 3 phase cable feeding into my house, although I
>>>> use only one of them.(In the dim past each house got current from
>>>> 1 of those 3 wires)
>>>
>>> My house?  Each house?  Please explain.
>>>
>> 3 houses, mine is the middle one, and each phase feeding 1 house.
>> That way, I end up with  a 3phase power cable.
>
> Why does the cable for the other two houses enter yours?  Row houses?
>
A row of 3. And why only one feed cable? I have no idea.

[toc] | [prev] | [next] | [standalone]


#461946

Fromkrw@notreal.com
Date2017-05-26 22:33 -0400
Message-ID<4aphic5qgdcirqmq1o3gjsnqurlnpl2g7n@4ax.com>
In reply to#461944
On Sat, 27 May 2017 04:25:17 +0200, Sjouke Burry
<burrynulnulfour@ppllaanneett.nnll> wrote:

>On 27.05.17 4:21, krw@notreal.com wrote:
>> On Sat, 27 May 2017 02:05:24 +0200, Sjouke Burry
>> <burrynulnulfour@ppllaanneett.nnll> wrote:
>>
>>> On 27.05.17 1:53, krw@notreal.com wrote:
>>>> On Sat, 27 May 2017 01:46:41 +0200, Sjouke Burry
>>>> <burrynulnulfour@ppllaanneett.nnll> wrote:
>>>>
>>>>> On 26.05.17 0:47, krw@notreal.com wrote:
>>>>>> On Thu, 25 May 2017 15:07:13 -0500, Jon Elson <jmelson@wustl.edu>
>>>>>> wrote:
>>>>>>
>>>>>>> rickman wrote:
>>>>>>>
>>>>>>>> No, 220 VAC is not common in the US, at least not in homes or offices.
>>>>>>>> I don't know what hospitals might have.
>>>>>>>
>>>>>>> Actually, 120/208 Wye service is quite common in larger offices.  Might not
>>>>>>> have it in the typical storefront-type building, but almost any multi-level
>>>>>>> office building will likely have that system.  It gives lots of 120 V
>>>>>>> single-phase outlets, and 208 V between any two hots.  Smaller air
>>>>>>> conditioners would have 3-phase compressors off the 208 mains.  The building
>>>>>>> I work in has 120/208 Wye in the offices, 120/208 Wye PLUS 230 Delta in the
>>>>>>> lab space and 480 in the mechanical areas.
>>>>>>>
>>>>>>> 3 Phase is VERY rare in single-family homes, but common in apartment
>>>>>>> buildings.  And, certainly, any hospital will have 3-phase panels throughout
>>>>>>> the building.
>>>>>>
>>>>>> 3-Phase will certainly be common in large apartment buildings but
>>>>>> it'll never be found inside a single apartment.  Think of the building
>>>>>> as a neighborhood.  ;-)
>>>>>>
>>>>> Hmm... I have a 220/380 3 phase cable feeding into my house, although I
>>>>> use only one of them.(In the dim past each house got current from
>>>>> 1 of those 3 wires)
>>>>
>>>> My house?  Each house?  Please explain.
>>>>
>>> 3 houses, mine is the middle one, and each phase feeding 1 house.
>>> That way, I end up with  a 3phase power cable.
>>
>> Why does the cable for the other two houses enter yours?  Row houses?
>>
>A row of 3. And why only one feed cable? I have no idea.

OK, makes sense.  I can see why they feed only one.  The meters for
all three units are on your wall, too, I suppose?  